HDA 5500 for HLB 1000 and CS 1000
- 12 -
Menu point
Setting
Setting range
Default setting
When CS 1000 is selected
Important:
The default settings of the upper and lower limits of channels 1 to 4 (LO.1 to LO.4 and Hi.1
to HI.4) correspond to the values for operating the HLB 1000 on the HDA 5500.
When operating the CS1000 on the HDA5500 please note that: The default setting ranges
pre-set in the CS 1000 for the analogue signal output forms HDA.ISO, HDA.SAE or
HDA.NAS must be changed as follows.
HDA.ISO signal:
LO.1 to
LO.4 =
0.0
Hi.1 to
HI.4 =
24.4
HDA.SAE or HDA.NAS signal:
LO.1 to
LO.4 =
0.0
Hi.1 to
HI.4 =
14.0
Allocation of switching output 1 (S.S.1)
Switching output 1 allocated to the signal
From
channel
1
Switching output 1 allocated to the signal
From
channel
2
Switching output 1 allocated to the signal
From
channel
3
Switching output 1 allocated to the signal
From
channel
4
Channel 1
Channel 2
Channel 3
Channel 4
Channel 1
Switching mode switching output 1 (S.M.1)
Switching output 1 set to switch point and
hysteresis mode
Switching output
1
set to switching window mode
SP
Win
SP
Switching direction switching output 1 (S.d.1)
Relay activated
Relay deactivated
on
oFF
on
Switch on delay switching output 1 (T.on1)
Time, in seconds, which must elapse once the particular switch
point has been reached or exceeded in order for a switching
function to occur.
0..99.99 s
0
Switch off delay switching output 1 (T.oF1)
Time, in seconds, which must elapse once the value has fallen
below the particular switch-back point in order for a switching
function to occur.
0..99.99 s
0