Poseidon 4002
– Manual
HW group
www.HW-group.com
ETHERNET
Interface
RJ45 (10BASE-T)
– 10 Mbps or 10/100 Mbps network compatible
Supported protocols
IP: ARP, TCP/IP (HTTP, Modbus over TCP, NTP, SMTP), UDP/IP (SNMP)
SNMP compatibility
Ver:1.00 compatible, some parts of the ver 2.0 implemented
SENSORS
Port
S1, S2, S3, S4
Type
HWg original accessories: 1-Wire or 1-Wire UNI
Connector
RJ11 (1-Wire Bus)
Sensors
Up to 12 sensors in total
Sensors distance
Up to 60m per each single port - 4x 60m in total
DRY CONTACT INPUTS
Port
I1, I2, I3, I4, I5, I6
Type
Digital Input (ready to NO/NC Dry or Wet contact)
Sensitivity
1 (On) = 0…500 Ω (Right pin from terminal block can be connected with 12V GND)
Max. distance
Up to 50m
OUTPUTS
Port / type
OUT1, OUT2 / Relay contacts (NC-COM-NO)
Max. load
up to 48W (4A/12V or 1A/48V)
State
Power up state (no state restart memory)
GSM MODEM
Port
RS-232 / Cannon DB9M
Type
Serial port (RxD, TxD, RTS, CTS, GND)
Usage
GSM modem / Serial setup configuration with Dip1=ON
POWER input
Port
POWER 9-15V DC
Type
Main device power input (typically 400 mA + external devices)
Connector
Jack (barrel, inner 2.5 mm outer 6.3 mm) & Terminal block (parallel connection)
POWER OUT
Port
12V, 12V, 12V (Terminal blocks)
Type
12V output for external device (GSM modem, sensors..)
- powered from power input (require external fuse for over current protections).
LED Status indicators
POWER
Green - power OK
LINK & Activity
Yellow - Ethernet connectivity
ALARM
Red - Any sensor in alarm state
GSM
Green
– GSM modem activity
DIP SWITCH
DIP1: Setup
ON = RS-232 Setup mode over serial port (RS-232 mode only)
Load defaults:
Toggle 3 times during first 5 seconds after power-up to load default settings.
DIP2: Security
ON = Security mode - remote configuration disabled
OFF = Non-Security mode - remote configuration enabled
Physical parameters
Temperature range
Operating: -10 to 65
°C / Storage: -25 to 85 °C
MTBF
> 90 000 hours
Dimensions / Weight
182 x 44 x 125 [mm] / 500 g
EMC
FCC Part 15, Class B, CE - EN 55022, EN 55024, EN 61000