HUMIDIFIRST
INSTALLATION PARAMETERS & GUIDELINES
MECHANICAL
1.
The supply air temperature to the humidifier modules should be between 40 F
and 122 F at 90% relative humidity or less.
2.
It is advisable that a safety drain pan be installed underneath the humidifier
module and piped to the nearest drain.
3.
The humidifier must be mounted level from front to back and from side to side.
WATER AND WATER PIPING
1.
Water supply pressure should be between 10 psi to 75 psi.
2.
Water supply temperature should be between 40 F to 100 F.
3.
Pure water, 2.5 parts per million (ppm) or cleaner, should be used in the
humidifier. Water dirtier that 10 ppm can introduce dust into the air, which will
eventually collect inside of the facility. Dirty water will normally not damage the
humidifier but will require more frequent humidifier maintenance.
4.
Reverse osmosis systems with de-ionization bottles or just de-ionization bottles,
alone, are typically used for water treatment. Please contact us for sizing and/or
selection of water treatment equipment. Undersized water treatment systems can
cause damage to the humidification system.
5.
Water piping to each humidifier should be designed for use with de-ionized water
ie. stainless steel, appropriate plastic, etc.
(check local building codes requirements)
ELECTRICAL
1.
Follow all local, State, and Federal wiring guidelines.
2.
Allowable voltage va/- 10%.
3.
The power source should be provided with a circuit breaker.