background image

 

15 

HUMIDIFIRST 

 

 

 

 

3.

 

The water solenoid valve does not shut off  (read this page completely before starting 
to troubleshoot): 

 

If the solenoid valve continues to allow water to pass when the humidifier power is 
shut off, then there may be dirt in the solenoid valve, preventing it from seating.  If 
the solenoid valve stops water flow when the humidifier power is shut off then it is 
most likely an electrical problem incorrectly holding the solenoid valve open (ie. float 
switch or relay).  Please note that the reed switches in a float switch may stick at 
times, causing a temporary problem.  Lighting strikes or bad power may cause this.  If 
this is an intermittent problem the float switch should be replaced. 
 
a. If an electrical problem is keeping the solenoid valve open: (Warning – only 
qualified technicians should do this test as the Humidifirst Master Panel must be 
energized while making electrical measurements)  
 
Call the factory to discuss the best way to test your humidifier.  Depending on the 
model of the humidifier, the solenoid control relay may be wired Normally Open 
(NO) or Normally Closed (NC).   

 

b. If the solenoid valve does not shut off when the humidifier power is turned “off”, 
dirt may be preventing the solenoid valve plunger from seating.  This permits water to 
leak through it, causing the humidifier to overflow. 

 

To inspect the valve for debris: 
 
1)     

Remove the nut that holds the coil in place 

2) 

Slide the coil housing off of the shaft 

3) 

Grip the end of the shaft that is nearest to the threads with a set of pliers 
and turn counter-clockwise until the shaft is loose.  Then continue turning 
the shaft by hand until it unthreads from the valve housing.  A spring-
loaded plunger will come out of the end of the shaft.  Confirm that there is 
no dirt on it or in the valve housing.  Blow through the housing to clear 
any dirt that may have accumulated.  

4)

 

      Reassemble the valve.   

5)

 

      To test the valve, connect water to the unit and see if water drips from the     

            water hose on the “discharge” side of the valve.  

 

c.

 

Confirm that the humidifier has not been deprived of water.  This can cause the  
solenoid valve to overheat and fail open.  Reverse osmosis water treatment systems 
can sometimes reduce water flow to the humidifiers and cause this to happen.  
Reduced water flow can occur when the water temperature drops or if the reverse 
osmosis membrane fails.  If this is the case, replace the valve. 

 
 

Summary of Contents for MIST-PAC SERIES

Page 1: ...HUMIDIFIRST HUMIDIFIRST ULTRASONIC HUMIDIFIERS OWNER S MANUAL FOR MIST PAC SERIES ULTRASONIC HUMIDIFIERS 7 21 05...

Page 2: ...r and controls 9 Positioning your humidifier module and Master Panel 10 Installation requirements 10 Installation Parameters Guidelines 11 Before you start your humidifier for the first time 12 Starti...

Page 3: ...t all play a role in the ability of a humidifier to maintain the relative humidity of a space Also some older buildings may form ice in colder temperatures on the outside walls due to humidified air s...

Page 4: ...s very small water droplets into the air approximately one micron in diameter similar in size to steam droplets The water droplets are so small that they evaporate almost immediately The water feeding...

Page 5: ...st be added to achieve your relative humidity requirements 2 Air conditioning When an air conditioner runs it removes moisture from the air This is known as Latent cooling If the air conditioner will...

Page 6: ...__________________________________ Zone _________________________________________ Indoor design conditions required Temperature ________ F Relative humidity _______ RH Outdoor ambient design condition...

Page 7: ...sions of humidifier modules Humidifier Capacity Power Weight Dimensions Number of Fan Module hr used lbs WxDxH in Transducers CFM MP 5 5 135 va 9 9 0 x 12 9 x 12 5 4 45 MP 15 15 380 va 12 21 0 x 12 9...

Page 8: ...1 04 PANEL SIZE 12 X 12 X 8 6 POWER CORD WITH PLUG ATTACHED 10 CONTROL POWER HARBNESS WITH QUICK CONNECTS PROVIDED 10 CORD TO HUMIDISTAT PANEL TO BE UL LISTED ENCLOSURE TO HAVE HIGH QUALITY FINISH WIT...

Page 9: ...generated The ultrasonic humidifier shall not produce any unacceptable noise The sound level shall not exceed 50 db at 5 feet from the humidifier module The ultrasonic humidifier shall not require a...

Page 10: ...ay cause failure of the fan s and internal electronic components See the Installation Parameters Guidelines on the following pages Locating the Master Panel The Master Panel can be mounted on an adjac...

Page 11: ...er that 10 ppm can introduce dust into the air which will eventually collect inside of the facility Dirty water will normally not damage the humidifier but will require more frequent humidifier mainte...

Page 12: ...humidifier is mounted correctly 4 Always have at least 10 PSI of water pressure connected to the humidifier module Caution a When water purification systems are used pressure drops may be substantial...

Page 13: ...e sure the system is ready to be started and that all water and electrical connections are correct Flip the circuit breakers to the on position before closing the lid 4 Plug the power cord from the Ma...

Page 14: ...s blown 2 If water does not flow into the humidifier body Check that there is power to the humidifier first and make sure that there is a call for humidifier operation turn the humidistat to the highe...

Page 15: ...ed NC b If the solenoid valve does not shut off when the humidifier power is turned off dirt may be preventing the solenoid valve plunger from seating This permits water to leak through it causing the...

Page 16: ...isfied a Turn the humidistat dial to on to make sure the humidistat is calling for the humidifier to operate b Check that there is power to the humidifier The power on switch should be lit c Check to...

Page 17: ...ducers may get coated with an oily substance typically coming from new PVC or stainless steel pipe If this is the case try washing the basin and transducer with a mild dishwasher liquid solution 2 Som...

Page 18: ...be rinsed completely 5 The mist diffuser should be cleaned and rinsed before it is replaced Disconnect the power cord to the Master control panel and check all the wiring connections for tightness Thi...

Page 19: ...ose to the desired set point of the space being humidified Calibration should only be done with a sling psychrometer To calibrate set the humidifier humidistat indicator to read the same as the indepe...

Page 20: ...e following checklist and return it to Humidifirst There will be no warranty of the equipment without the form being completed and returned in a timely manner The End User Owner of the Humidification...

Page 21: ...se the mist to re circulate into the intake fans ___________ yes ___________no e Is the humidifier module mounted level from side to side __________ yes f Is the humidifier module mounted level from f...

Page 22: ...g start up 7 Have all wire connections in the Master control panel tightened Make sure the power to the panel has been turned off while tightening __________ yes ___________ no 8 The humidifier has be...

Page 23: ...23 HUMIDIFIRST HUMIDIFIRST ULTRASONIC HUMIDIFIERS 1520 Neptune Dr Suite A Boynton Beach FL 33426 561 752 1936 FAX 801 760 2777 www humidifirst com...

Reviews: