background image

 

HUMIDIFIRST 

 

 

 

 

 

HUMIDIFIRST 

humidifier sizing calculations

 

 
 
 
When calculating the humidification loads of a space we will generalize and assume that 
the majority of the humidification load will come from two areas: 
 
1.

 

Ventilation, Exhaust, or Infiltration of air: Most buildings have air exchanges with 
the outside because of one or more of these three items. 

 

A.

 

Ventilation is a result of air conditioning systems bringing outside air in to 
provide fresh air to the inhabitants. 

B.

 

Exhaust is the mechanical removal of air from a space when processes inside of 
the building require the removal of dirty, hot or unwanted air. 

C.

 

Infiltration occurs when air comes into a space from outside.  Air may come in 
through small openings around doors, windows, ceilings, etc.  Also, infiltration 
often occurs from frequent opening of doors.   

 

For each Cubic Foot per Minute (CFM) of outside air that is brought into the space, 
moisture must be added to achieve your relative humidity requirements. 

 
2.

 

Air conditioning: When an air conditioner runs, it removes moisture from the air.  
This is known as Latent cooling.  If the air conditioner will be running during your 
humidification season, you must take this dehumidification process into account.     
The cooling ability of an air conditioner is normally rated by the manufacturer and is 
stated in Sensible and Total cooling capacity in btu’s per hour.  Subtract the Sensible 
cooling capacity from the Total cooling capacity to get the Latent cooling capacity.  
For every 1000 btu’s/hour of Latent cooling capacity you will need to add one pound 
of moisture. 

 
 
Please note that there are other factors that can add to your humidification requirements, 
such as moisture absorption of items in your space.   We generally ignore them because 
most often they play only a minor part of your humidification requirements.  Contact us 
if you think you have unique requirements. 
 
See the next page for a simple chart that you can fill in and send to us.  We would be 
happy to assist you with sizing your humidification system. 
 
 
 
 
 

Summary of Contents for MIST-PAC SERIES

Page 1: ...HUMIDIFIRST HUMIDIFIRST ULTRASONIC HUMIDIFIERS OWNER S MANUAL FOR MIST PAC SERIES ULTRASONIC HUMIDIFIERS 7 21 05...

Page 2: ...r and controls 9 Positioning your humidifier module and Master Panel 10 Installation requirements 10 Installation Parameters Guidelines 11 Before you start your humidifier for the first time 12 Starti...

Page 3: ...t all play a role in the ability of a humidifier to maintain the relative humidity of a space Also some older buildings may form ice in colder temperatures on the outside walls due to humidified air s...

Page 4: ...s very small water droplets into the air approximately one micron in diameter similar in size to steam droplets The water droplets are so small that they evaporate almost immediately The water feeding...

Page 5: ...st be added to achieve your relative humidity requirements 2 Air conditioning When an air conditioner runs it removes moisture from the air This is known as Latent cooling If the air conditioner will...

Page 6: ...__________________________________ Zone _________________________________________ Indoor design conditions required Temperature ________ F Relative humidity _______ RH Outdoor ambient design condition...

Page 7: ...sions of humidifier modules Humidifier Capacity Power Weight Dimensions Number of Fan Module hr used lbs WxDxH in Transducers CFM MP 5 5 135 va 9 9 0 x 12 9 x 12 5 4 45 MP 15 15 380 va 12 21 0 x 12 9...

Page 8: ...1 04 PANEL SIZE 12 X 12 X 8 6 POWER CORD WITH PLUG ATTACHED 10 CONTROL POWER HARBNESS WITH QUICK CONNECTS PROVIDED 10 CORD TO HUMIDISTAT PANEL TO BE UL LISTED ENCLOSURE TO HAVE HIGH QUALITY FINISH WIT...

Page 9: ...generated The ultrasonic humidifier shall not produce any unacceptable noise The sound level shall not exceed 50 db at 5 feet from the humidifier module The ultrasonic humidifier shall not require a...

Page 10: ...ay cause failure of the fan s and internal electronic components See the Installation Parameters Guidelines on the following pages Locating the Master Panel The Master Panel can be mounted on an adjac...

Page 11: ...er that 10 ppm can introduce dust into the air which will eventually collect inside of the facility Dirty water will normally not damage the humidifier but will require more frequent humidifier mainte...

Page 12: ...humidifier is mounted correctly 4 Always have at least 10 PSI of water pressure connected to the humidifier module Caution a When water purification systems are used pressure drops may be substantial...

Page 13: ...e sure the system is ready to be started and that all water and electrical connections are correct Flip the circuit breakers to the on position before closing the lid 4 Plug the power cord from the Ma...

Page 14: ...s blown 2 If water does not flow into the humidifier body Check that there is power to the humidifier first and make sure that there is a call for humidifier operation turn the humidistat to the highe...

Page 15: ...ed NC b If the solenoid valve does not shut off when the humidifier power is turned off dirt may be preventing the solenoid valve plunger from seating This permits water to leak through it causing the...

Page 16: ...isfied a Turn the humidistat dial to on to make sure the humidistat is calling for the humidifier to operate b Check that there is power to the humidifier The power on switch should be lit c Check to...

Page 17: ...ducers may get coated with an oily substance typically coming from new PVC or stainless steel pipe If this is the case try washing the basin and transducer with a mild dishwasher liquid solution 2 Som...

Page 18: ...be rinsed completely 5 The mist diffuser should be cleaned and rinsed before it is replaced Disconnect the power cord to the Master control panel and check all the wiring connections for tightness Thi...

Page 19: ...ose to the desired set point of the space being humidified Calibration should only be done with a sling psychrometer To calibrate set the humidifier humidistat indicator to read the same as the indepe...

Page 20: ...e following checklist and return it to Humidifirst There will be no warranty of the equipment without the form being completed and returned in a timely manner The End User Owner of the Humidification...

Page 21: ...se the mist to re circulate into the intake fans ___________ yes ___________no e Is the humidifier module mounted level from side to side __________ yes f Is the humidifier module mounted level from f...

Page 22: ...g start up 7 Have all wire connections in the Master control panel tightened Make sure the power to the panel has been turned off while tightening __________ yes ___________ no 8 The humidifier has be...

Page 23: ...23 HUMIDIFIRST HUMIDIFIRST ULTRASONIC HUMIDIFIERS 1520 Neptune Dr Suite A Boynton Beach FL 33426 561 752 1936 FAX 801 760 2777 www humidifirst com...

Reviews: