VI. Power cable withstand voltage test method
1.
Disconnect all electrical equipment connected to the tested cable.
2.
Use a megger to test the insulation parameters of each phase of the cable, and carry out the
ultra-low frequency withstand voltage test only after the test isqualified.
3.
Set the test voltage value: Umax = 3uo, where uo is the rated phase voltage ofthe cable.
Example 1: cable parameter: the rated line voltage is 10kV, and the rated phase voltage uo =
6kV, so the test voltage setting value is:
Umax = 3uo = 18kV
See Table 4 for the setting value of 0.1Hz ultra-low frequency test voltage of various rubber and
plastic insulated power cables.
Table 4 0.1Hz ultra-low frequency test voltage and time of various rubber plastic insulated
power cables.
Rated
voltage
U
0
/U
S
(kV)
Handover test
Preventive experiment
multi
ple
Test
voltage
(
kV
)
Test time
(
mins
)
multip
le
Test
voltage
(
kV
)
Test time
(
mins
)
1.8/3
3U
0
5
60
3U
0
5
15
3.6/6
3U
0
11
60
3U
0
11
15
6/6
3U
0
18
60
3U
0
18
15
6/10
3U
0
18
60
3U
0
18
15
8.7/10
3U
0
26
60
3U
0
26
15
12/20
3U
0
36
60
3U
0
36
15
21/35
3U
0
63
60
3U
0
63
15
26/35
3U
0
78
60
3U
0
78
15
Note: UN is the rated voltage of the cable, and uo is the phase voltage of the cable.
4.
Test time: 60 minutes for handover test and 15 minutes for preventive test.
5.
Setting current value of overcurrent protection:
Estimation method of capacitive current (or leakage current) of ultra-low frequency withstand
voltage test article: