6
●
Manual voltage regulation function
Digital
Insulation value
( >
greater than
; <
less than
)
Measured time
actual voltage
Battery Indicator
H.V
warning
Leakage current
1mA=1000uA
1uA =1000nA
Set Voltage
Regulating key
Soft key
Description
Regulating key +
,
By a voltage rise of 10V, long time boost up,
the fastest up to 600V per second.
Regulating key -
,
According to a voltage drop 10V, long time
step-down speed up, the fastest u
Stop
measuring
In manual voltage regulation, due to the use of 3 and 4 keys,
only 1, 2 keys and start stop keys can be used to stop the
measurement operation.
When the test time or manual stopped, display shows as shown in the table of the
soft keys.
Soft key
Description
OFF
Power Off (No operation, 3 minutes automatic shutdown)
Back
Return to the main menu
H.V
Manual
、
500V
、
1000V
、
2500V
、
5000V
、
10000V
、
15000V
、
20000V
Rt
Veiw 15S
、
30S
、
60S
、
600S Insulation value
V. Instrument using
measured DAR
:
1. Select more than 1 minute length measurement.
2. Select the appropriate voltage and start.
3. The instrument automatically record 15 s and 60 s resistance, and calculate the
absorption than after 60 seconds.
Absorption ratio calculation method: DAR = R60 / R15;
measured PI :
1. Select more than 10 minute length measurement.
2. Select the appropriate voltage and start.
3. The instrument automatically record 15S, 60S and 600S resistance, and calculate the
polarization index after 600 seconds.
Set Voltage: