UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
A Alarm List
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
157
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
properly.
0043-2
The fan is faulty.
Check the fan or replace the
bypass module.
0043-3
The fan is faulty.
The fan
monitoring cable
is faulty.
1.
Replace the fan.
2.
Check the fan monitoring
cable.
0043-4
0047-1
Not ready
Critical
The ready switch is
OFF.
Close the ready switch.
0060-4
Inverter abnormal
Critical
A load
short-circuit
occurs.
A short circuit
occurs inside the
module. (This
fault seldom
occurs.)
1.
Check load cable distributions.
2.
If load cable distributions are
normal, replace the power
module.
0061-2
Inverter alarm
Minor
The I2C bus is
not normal.
The E2PROM is
faulty.
1.
Rectify the fault and check
whether the alarm is cleared.
2.
If the alarm is generated again,
replace the power module.
0061-7
Inverter alarm
Minor
The bypass
waveform is not
normal.
If not all modules generate the
alarm, start the UPS, transfer it
to normal mode, and replace
the faulty module.
If all modules generate the
alarm, open the bypass input
circuit breaker. After the
inverter relay is closed, close
the bypass input circuit
breaker 10 seconds later.
0564-1
Overload timeout
Critical
The load is
excessive.
Derating reduces
the rated system
power.
The module is
damaged.
1.
Check that there is no
overload.
2.
Check that the module power
is not derated due to a fan
fault.
3.
If the alarm persists, replace
the power module.
0565-1
Load impact
transfer-to-bypass
Minor
A large-power
RCD load is
instantly
connected, or the
1.
Check the load.
2.
If the load is normal, replace
the power module.