UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
4 User Interface
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
112
Item
Description
Default
Value
Value
Range
overtemp.
Table 4-17
Battery Setting
Item
Description
Default
Value
Value
Range
Bat mode shut
In battery mode, the UPS can automatically
power off according to the preset shutdown
delay time. If the parameter is disabled, this
function is not available.
Disable
Disable,
Enable
Backup time
warning
An alarm is generated if this parameter is set to
Enable and the backup time is less than the
warning threshold.
Disable
Disable,
Enable
Remain. cap.
warning
An alarm is generated if this parameter is set to
Enable and the remaining capacity is less than
the warning threshold.
Disable
Disable,
Enable
Thres. of low
batt. SOC over
dry contact (%)
If an output dry contact is set to Low battery
SOC, and the battery SOC is lower than this
threshold, the output dry contact will output
signals.
70
5–80
Thres. of low
batt. volt. over
dry contact
(V/cell)
If an output dry contact is set to Batt. Volt.
Below Threshold, and the battery voltage is
lower than this threshold, the output dry contact
will output signals.
1.70
1.70–2.10
4.2.2.2 Comm. Config. Page
Open the
Comm. Config.
page to set communications information.
Figure 4-40
Comm. Config.
4.2.2.3 Control Page
Open the
Control
page to control the system running.