UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
A Alarm List
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
156
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
board may be faulty. Replace
the board.
0032-1
Battery overvoltage
protection
Critical
The battery
voltage is greater
than the upper
threshold.
The configured
number of
batteries is less
than the actual
number.
The actual
number of
batteries does not
meet
requirements.
1.
Check the battery voltage.
2.
Check that the configured
number of batteries matches
the actual number.
3.
Check that the actual number
of batteries meets
requirements.
0036-2
Battery
maintenance
reminder
Warning
The time for
maintenance arrives.
Maintain the batteries.
0037-1
Battery
undervoltage
Critical
The UPS has
worked in battery
mode for an
extended amount
of time.
The charger is
faulty.
1.
Check whether the battery
voltage is normal.
2.
Check whether the output is
overloaded.
3.
Check whether any battery is
damaged. If yes, replace the
battery.
4.
Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
0040-7
Rectifier abnormal
Critical
The fan for the
power module is
not functioning
properly.
The air channel
for the power
module is
obstructed.
1.
Check that the air channel for
the module is free from
blockage.
2.
Check whether the fans are
functioning properly. Replace
the power module if the fans
are faulty.
0043-1
Fan abnormal
Critical
The fan for the
power module is
abnormal.
The fan
monitoring cable
for the power
module is not
working
Replace the faulty power module.