UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
4 User Interface
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
100
Figure 4-28
Maintenance 2
Choose
Monitoring
>
Param. Settings
>
System Settings
on the WebUI, if the
Bus capa. life
is set
to
Enable
, the
Maintenance
is displayed on the
Bus Capa. Life
screen.
Battery Maint.
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.
Battery maintenance includes
Shallow Dis. Test
and
Capacity Test
.
Figure 4-29
Battery Maint.
Item
Description