Item

Expected Result

Measures

Charge 
current

≤ 2 A (standard model)
≤ 8 A (long backup time 
model)

If the charge current is incorrect, contact Huawei
technical support.

Battery string 
charge 
voltage

Equalized voltage 14.1 V x 
Number of batteries 
(tolerance 

±

1%)

Float voltage 13.5 V x 
Number of batteries 
(tolerance 

±

1%)

1. If the voltage drop between the battery 

string output terminals and the battery input 
terminals at the UPS host side is greater than 
1% of the battery string voltage, check 
whether the cable between the battery string 
and the UPS is excessively long, or the cable 
diameter is excessively small.

2. Check whether the equalized charging 

voltage and float charging voltage are 
correctly set for the UPS host.

3. If the fault persists, contact Huawei technical 

support.

Battery 
appearance

1. The battery shell is intact, 

without acid leaks, 
deformation, or bulges.

2. The battery is free from 

dust or dirt.

1. Take photos of any deformed or faulty parts 

of batteries.

2. Check and record the charge voltage and 

current of the battery string as well as the 
voltage of each battery.

3. Check the battery surface temperature.

4. Keep deformed and bulged faulty batteries 

still for 30 minutes and then check and 
record open-circuit voltage of the faulty 
battery.

5. If the fault persists, contact Huawei technical 

support.

Battery 
management 
parameters

Parameters settings of 
battery number, battery 
capacity, battery charge 
voltage, battery charge 
current, and EOD setting 
values meet requirements. 
The capacity value matches 
the actual value.

Set parameters correctly.

Battery alarm

No battery alarm is 
generated.

Identify the cause based on the alarm 
information.

Battery 
connection

Battery terminals and cables 
are in good contact.

Ensure that battery terminals and cables are in 
good contact.

Battery 

operating 
temperature

1. The difference between 

temperature reported by 
the battery temperature 
sensor and the actual 
temperature is less than 
2ºC.

2. The service temperature 

of a working battery does 
not exceed 45ºC.

1. Identify the cause of the false temperature 

sensor alarm.

2. Identify the cause of the abnormal battery 

operating temperature.

3. If the fault persists, contact Huawei technical 

support.

2

Battery Maintenance

Summary of Contents for UPS2000-A-10KTTL-P

Page 1: ...0 HUAWEI TECHNOLOGIES CO LTD UPS2000 A 6 kVA 10 kVA Quick Guide Issue 04 Part Number 31506975 Date 2020 09 11 ...

Page 2: ...me 67 UPS2000 A 10KTTL S 10 kVA standard version with long backup time 21 UPS2000 A 10KTTS P 10 kVA professional version with standard backup time 79 UPS2000 A 10KTTL P 10 kVA professional version with long backup time 22 Introduction 6 kVA 10 kVA Standard Version with Standard Backup Time 6 kVA 10 kVA Standard Version with Long Backup Time 1 AC input circuit breaker 2 Optional card slot under the...

Page 3: ...urity protection mechanism supported 5 MBS port 6 Parallel cable port 7 Micro switch under the cover 8 Maintenance bypass circuit breaker 9 AC output circuit breaker 10 AC input terminal under the cover 11 Single UPS jumper terminal under the cover 12 AC output terminal under the cover 13 Battery wiring terminal under the cover UG10000006 1 2 3 4 5 10 6 11 12 9 8 7 UG10000007 1 2 3 4 5 6 9 8 7 10 ...

Page 4: ...ong backup time Move the UPS to the installation position and press down the brake pads on the casters to secure the UPS If mounting brackets are configured install the mounting brackets on the UPS using M6x12 bolt and secure the UPS to the floor using M12x60 expansion bolts Brake pad Installation a Single UPS 2 Installing AC Input and Output Power Cables 1 Connect UPS AC input and output terminal...

Page 5: ...N m UPS2000 A 6KTTL S M4 6 PCS 1 4 N m UPS2000 A 6KTTL S M5 6 PCS 2 8 N m 6 kVA 10 kVA Professional Version with Standard Backup Time 6 kVA 10 kVA Professional Version with Long Backup Time UPS2000 A 6KTTS P M4 6 PCS 1 4 N m UPS2000 A 10KTTS P M5 6 PCS 2 8 N m UPS2000 A 6KTTL P M4 6 PCS 1 4 N m UPS2000 A 6KTTL P M5 6 PCS 2 8 N m UG10000089 UG10000090 Mains AC load Mains AC load Short circuit bar S...

Page 6: ...ker for the 10 kVA model 3 One or two battery boxes can be connected For details see the ESS 240V12 2x 9AhBPVBA 7AhBPVBA Quick installation Guide If longer backup time is required choose a battery rack Model UPS2000 A 6KTTL S UPS2000 A 6KTTL P UPS2000 A 10KTTL S UPS2000 A 10KTTL P Wiring Terminal BATT BATT External Circuit Breaker 50 A 63 A Cable Cross sectional Area 6 mm2 10 mm2 Terminal Type OT ...

Page 7: ...down Back On the default screen in inverter mode hold down ESC for more than 5 seconds Release the button when you hear a beep tone The inverter shuts down On any other screen press ESC to return to the upper level menu the default screen is the upper level screen for the main menu screen Up Press or to scroll upward or downward You can set a value by using the list or step increase or decrease Do...

Page 8: ...ng battery parameters compromises battery safety and battery backup time For details about parameter settings see the UPS2000 A 6 kVA 10 kVA User Manual 2 Set system parameters with caution because the settings determine normal UPS operation Setting Key UPS Parameters 5 2 Parameter UI Display Remarks Output voltage level 01 VOT For standard version the optional values include 220 V 230 V and 240 V...

Page 9: ...mum charge current in equalized charge mode based on actual conditions 6 kVA or 10 kVA UPS with standard backup time 2 A not configurable 6 kVA or 10 kVA UPS with long backup time 4 A by default value range 1 8 A at an interval of 0 5 A Set the output voltage level Start Set the output frequency system Set the number of batteries End No UPS with long backup time Check that the input is normal UPS ...

Page 10: ...s beyond the configured range the UPS has no output 1 Shut down loads 2 Perform shutdown operations on the UPS The inverter shuts down and the UPS transfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 3 Open the upstream AC input circuit breaker for the UPS the AC input circuit breakers on the rear panel of the UPS the AC output circuit breakers on the...

Page 11: ...d version does not 2 This section describes how to install a 1 1 parallel system A maximum of four UPSs can be connected in parallel 6 kVA 10 kVA Professional Version with Standard Backup Time UPS2000 A 6KTTS P M4 12 PCS 1 4 N m UPS2000 A 10KTTS P M5 12 PCS 2 8 N m 1 2 3 4 5 6 1 AC input circuit breaker of UPS 1 2 AC input circuit breaker of UPS 2 3 AC output circuit breaker of UPS 1 4 AC output c...

Page 12: ...PORT1 PORT2 UPS 2 UPS 1 This section describes the cable connection method for a 1 1 parallel system Refer to this method to connect the cables in other scenarios UPS2000 A 6KTTL P M4 12 PCS 1 4 N m UPS2000 A 10KTTL P M5 12 PCS 2 8 N m UPS 1 UPS 2 External power distribution provide by the customer Mains AC load 1 AC input circuit breaker of UPS 1 2 AC input circuit breaker of UPS 2 3 AC output ci...

Page 13: ...as passed all check items described in chapter 5 Verifying the Installation Close the external battery circuit breakers if there are Close the general AC input circuit breaker for UPSs each branch input circuit breaker and the AC input circuit breakers on the rear panels of UPS 1 and UPS 2 Start End No Start the UPS in battery mode Yes Start the UPS in normal mode Powering On the UPS 6 1 Setting K...

Page 14: ...nsfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 1 Shut down loads 2 Perform shutdown operations on each UPS in the parallel system All inverters shut down at the same time and the parallel system transfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 3 Open the AC input circuit breaker on each UPS the gen...

Page 15: ...1 VOT Output voltage level 02 FRE Output frequency system 03 BVU Maximum bypass voltage 04 BVL Minimum bypass voltage 05 NO Number of batteries 06 CAP Total battery capacity 07 CL Charge current limit 08 EOD EOD mode 09 DT Discharge time protection setting 10 ECO ECO mode enabling 11 VU Maximum ECO voltage 12 VL Minimum ECO voltage 13 FR ECO frequency range 14 S P Single UPS or parallel system ava...

Page 16: ...ranges and no fault or alarm information is displayed If an alarm is present rectify the fault by checking the device status and parameters Abnormal noise No abnormal noise is generated Check where the abnormal noise comes from especially fans input and output transformer if configured If the problem is not resolved contact Huawei technical support Cleanliness Wipe the cabinet surface using a whit...

Page 17: ...and current of the battery string as well as the voltage of each battery 3 Check the battery surface temperature 4 Keep deformed and bulged faulty batteries still for 30 minutes and then check and record open circuit voltage of the faulty battery 5 If the fault persists contact Huawei technical support Battery management parameters Parameters settings of battery number battery capacity battery cha...

Page 18: ...ads and restart the UPS The Mains indicator is off The mains voltage or frequency exceeds the UPS input range Use a multimeter to check that the input voltage and frequency meet specifications The battery discharge time is much less than the standard time Batteries are not fully charged The battery performance deteriorates Charge batteries for more than 8 hours when the mains is normal Test the di...

Page 19: ...ecome normal and manually clear the alarm Abnorma l BPS volt 0A 1 Possible cause The bypass input voltage is abnormal Measure Check whether the bypass input voltage is out of the specified range If the voltage is out of the specified range change the range setting or wait for the bypass input to recover 2 Possible cause The bypass frequency is out of the 45 55 Hz mapping to 50 Hz or 55 65 Hz mappi...

Page 20: ...leared Possible cause The number of batteries configured is less than the actual number of batteries Measure Check whether the number of batteries is correctly set Battery overvoltage protection 20 1 Possible cause The number of batteries configured is less than the actual number of batteries Measure Check that the configured number of batteries is consistent with the actual number Possible cause ...

Page 21: ...nected are loose Measure Check that parallel cables are securely connected Possible cause Parallel cables are damaged Measure Replace the parallel cables 2 4 5 Parallel cable alarm 54 2 Possible cause The parallel cables connected are loose Measure Check that parallel cables are securely connected Possible cause The parallel cables are damaged Measure Replace the parallel cables 3 EPO 55 1 Possibl...