UG10000082
1
Installing the UPS
10
2
Installing AC Input and Output Power Cables
1. Connect UPS AC input and output terminals L, N correctly. For a UPS with long backup time,
connect the battery terminals correctly.
2. Before connecting cables, ensure that the input circuit breaker and output circuit breaker
are OFF. For a UPS with long backup time, ensure that the battery circuit breakers are OFF.
Perform all tasks with the power off.
Refer to the UPS installation method on page 3 to install each UPS in the parallel system.
Installation Parallel System
1. The professional version supports parallel connection, and the standard version does not.
2. This section describes how to install a 1+1 parallel system. A maximum of four UPSs can be
connected in parallel.
6 kVA/10 kVA Professional Version with Standard Backup Time
UPS2000-A-6KTTS-P
M4 (12 PCS)
1.4 N•m
UPS2000-A-10KTTS-P
M5 (12 PCS)
2.8 N•m
1
2
3
4
5
6
(1) AC input circuit breaker
of UPS 1
(2) AC input circuit breaker
of UPS 2
(3) AC output circuit
breaker of UPS 1
(4) AC output circuit
breaker of UPS 2
(5) General AC input circuit
breaker of the parallel
system
(6) General AC output
circuit breaker of the
parallel system
Mains
AC
load
For a single UPS, install a short-circuit bar between JP1 and JP2. For a parallel system,
do not install it. When transferring from single mode to parallel mode, confirm that the short-
circuit bar is removed.
UPS 2
UPS 1
External power
distribution
(provide by the
customer)