4
6 kVA/10 kVA Standard Version
with Standard Backup Time
Model
UPS2000-A-6KTTS-S
UPS2000-A-6KTTL-S
UPS2000-A-6KTTS-P
UPS2000-A-6KTTL-P
UPS2000-A-10KTTS-S
UPS2000-A-10KTTL-S
UPS2000-A-10KTTS-P
UPS2000-A-10KTTL-P
Wiring Terminal
AC INPUT
AC OUTPUT
AC INPUT
AC OUTPUT
External Circuit Breaker
50 A/D
63 A/D
Earth Leakage Circuit Breaker
100 mA
-
100 mA
-
Cable Cross-sectional Area
6 mm
2
10 mm
2
Terminal Type
OT-6 mm
2
-M4 terminal
OT-10 mm
2
-M6 terminal
6 kVA/10 kVA Standard Version
with Long Backup time
UPS2000-A-6KTTS-S
M4 (6 PCS)
1.4 N•m
UPS2000-A-10KTTS-S
M5 (6 PCS)
2.8 N•m
UPS2000-A-6KTTL-S
M4 (6 PCS)
1.4 N•m
UPS2000-A-6KTTL-S
M5 (6 PCS)
2.8 N•m
6 kVA/10 kVA Professional Version
with Standard Backup Time
6 kVA/10 kVA Professional Version
with Long Backup Time
UPS2000-A-6KTTS-P
M4 (6 PCS)
1.4 N•m
UPS2000-A-10KTTS-P
M5 (6 PCS)
2.8 N•m
UPS2000-A-6KTTL-P
M4 (6 PCS)
1.4 N•m
UPS2000-A-6KTTL-P
M5 (6 PCS)
2.8 N•m
UG10000089
UG10000090
Mains
AC
load
Mains
AC
load
Short-
circuit
bar
Short-
circuit
bar
Mains
AC
load
Mains
AC
load
1. For a single UPS, install a short-circuit bar between JP1 and JP2. For a parallel system, do not
install it. When transferring from single mode to parallel mode, confirm that the short-circuit
bar is removed.
2. The professional version supports the dual-live wire system. Connect the L1 and L2 wires
respectively to the L and N terminals on the UPS.