background image

Alarm 
Name

Alar
m ID

Alarm 
Cause 
ID

Repair Proposal

Abnorma
l mains 
volt.

01

1

Possible cause: The mains voltage exceeds 280 V.
Measure: Check the mains input voltage, If the voltage exceeds 
272 V, wait for the mains to recover.

2

Possible cause: The mains voltage is less than 80 V. Measure: 
Check the mains input voltage, if the voltage is less than 88 V, 
wait for the mains to recover.

Possible cause: The input fuse is blown.

Measure: Check the status of the input fuse.

3

Possible cause: The mains frequency is out of the 45–55 Hz 
(mapping to 50 Hz) or 55–65 Hz (mapping to 60 Hz) range.

Measure: Check the mains input frequency. If the frequency is 

out of the normal range, wait for the mains to recover.

Possible cause: The input fuse is blown.

Measure: Check the status of input fuses.

4

Possible cause: The mains voltage is frequently abnormal.
Measure: Check the mains input voltage. If the voltage is abnormal, 
wait for the mains voltage to become normal and manually clear 
the alarm.

Abnorma
l BPS volt.

0A

1

Possible cause: The bypass input voltage is abnormal.
Measure: Check whether the bypass input voltage is out of the 
specified range. If the voltage is out of the specified range, change 
the range setting or wait for the bypass input to recover.

2

Possible cause: The bypass frequency is out of the 45–55 Hz 
(mapping to 50 Hz) or 55–65 Hz (mapping to 60 Hz) range.
Measure: Check the bypass input frequency. If the frequency is out 
of the normal range, wait for the bypass power supply to recover.

Batt. 
reverse

14

1

Possible cause: The positive and negative battery terminals are 
reversely connected.
Measure: Check the battery installation, and install batteries again.

No 
battery

16

1

Possible cause: No batteries are connected.

Measure: Connect batteries.

Possible cause: The batteries are in poor contact. 

Measure: Check the battery cable connection. If battery cables 

are loose, tighten the cables.

18

1. For more alarm handling, see the 

UPS2000-A-(6 kVA-10 kVA) User Manual

.

2. Clear automatically detected and manually cleared (ADMC) alarms as shown in the 

figures below.

Alarm Handling 

Summary of Contents for UPS2000-A-10KTTL-P

Page 1: ...0 HUAWEI TECHNOLOGIES CO LTD UPS2000 A 6 kVA 10 kVA Quick Guide Issue 04 Part Number 31506975 Date 2020 09 11 ...

Page 2: ...me 67 UPS2000 A 10KTTL S 10 kVA standard version with long backup time 21 UPS2000 A 10KTTS P 10 kVA professional version with standard backup time 79 UPS2000 A 10KTTL P 10 kVA professional version with long backup time 22 Introduction 6 kVA 10 kVA Standard Version with Standard Backup Time 6 kVA 10 kVA Standard Version with Long Backup Time 1 AC input circuit breaker 2 Optional card slot under the...

Page 3: ...urity protection mechanism supported 5 MBS port 6 Parallel cable port 7 Micro switch under the cover 8 Maintenance bypass circuit breaker 9 AC output circuit breaker 10 AC input terminal under the cover 11 Single UPS jumper terminal under the cover 12 AC output terminal under the cover 13 Battery wiring terminal under the cover UG10000006 1 2 3 4 5 10 6 11 12 9 8 7 UG10000007 1 2 3 4 5 6 9 8 7 10 ...

Page 4: ...ong backup time Move the UPS to the installation position and press down the brake pads on the casters to secure the UPS If mounting brackets are configured install the mounting brackets on the UPS using M6x12 bolt and secure the UPS to the floor using M12x60 expansion bolts Brake pad Installation a Single UPS 2 Installing AC Input and Output Power Cables 1 Connect UPS AC input and output terminal...

Page 5: ...N m UPS2000 A 6KTTL S M4 6 PCS 1 4 N m UPS2000 A 6KTTL S M5 6 PCS 2 8 N m 6 kVA 10 kVA Professional Version with Standard Backup Time 6 kVA 10 kVA Professional Version with Long Backup Time UPS2000 A 6KTTS P M4 6 PCS 1 4 N m UPS2000 A 10KTTS P M5 6 PCS 2 8 N m UPS2000 A 6KTTL P M4 6 PCS 1 4 N m UPS2000 A 6KTTL P M5 6 PCS 2 8 N m UG10000089 UG10000090 Mains AC load Mains AC load Short circuit bar S...

Page 6: ...ker for the 10 kVA model 3 One or two battery boxes can be connected For details see the ESS 240V12 2x 9AhBPVBA 7AhBPVBA Quick installation Guide If longer backup time is required choose a battery rack Model UPS2000 A 6KTTL S UPS2000 A 6KTTL P UPS2000 A 10KTTL S UPS2000 A 10KTTL P Wiring Terminal BATT BATT External Circuit Breaker 50 A 63 A Cable Cross sectional Area 6 mm2 10 mm2 Terminal Type OT ...

Page 7: ...down Back On the default screen in inverter mode hold down ESC for more than 5 seconds Release the button when you hear a beep tone The inverter shuts down On any other screen press ESC to return to the upper level menu the default screen is the upper level screen for the main menu screen Up Press or to scroll upward or downward You can set a value by using the list or step increase or decrease Do...

Page 8: ...ng battery parameters compromises battery safety and battery backup time For details about parameter settings see the UPS2000 A 6 kVA 10 kVA User Manual 2 Set system parameters with caution because the settings determine normal UPS operation Setting Key UPS Parameters 5 2 Parameter UI Display Remarks Output voltage level 01 VOT For standard version the optional values include 220 V 230 V and 240 V...

Page 9: ...mum charge current in equalized charge mode based on actual conditions 6 kVA or 10 kVA UPS with standard backup time 2 A not configurable 6 kVA or 10 kVA UPS with long backup time 4 A by default value range 1 8 A at an interval of 0 5 A Set the output voltage level Start Set the output frequency system Set the number of batteries End No UPS with long backup time Check that the input is normal UPS ...

Page 10: ...s beyond the configured range the UPS has no output 1 Shut down loads 2 Perform shutdown operations on the UPS The inverter shuts down and the UPS transfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 3 Open the upstream AC input circuit breaker for the UPS the AC input circuit breakers on the rear panel of the UPS the AC output circuit breakers on the...

Page 11: ...d version does not 2 This section describes how to install a 1 1 parallel system A maximum of four UPSs can be connected in parallel 6 kVA 10 kVA Professional Version with Standard Backup Time UPS2000 A 6KTTS P M4 12 PCS 1 4 N m UPS2000 A 10KTTS P M5 12 PCS 2 8 N m 1 2 3 4 5 6 1 AC input circuit breaker of UPS 1 2 AC input circuit breaker of UPS 2 3 AC output circuit breaker of UPS 1 4 AC output c...

Page 12: ...PORT1 PORT2 UPS 2 UPS 1 This section describes the cable connection method for a 1 1 parallel system Refer to this method to connect the cables in other scenarios UPS2000 A 6KTTL P M4 12 PCS 1 4 N m UPS2000 A 10KTTL P M5 12 PCS 2 8 N m UPS 1 UPS 2 External power distribution provide by the customer Mains AC load 1 AC input circuit breaker of UPS 1 2 AC input circuit breaker of UPS 2 3 AC output ci...

Page 13: ...as passed all check items described in chapter 5 Verifying the Installation Close the external battery circuit breakers if there are Close the general AC input circuit breaker for UPSs each branch input circuit breaker and the AC input circuit breakers on the rear panels of UPS 1 and UPS 2 Start End No Start the UPS in battery mode Yes Start the UPS in normal mode Powering On the UPS 6 1 Setting K...

Page 14: ...nsfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 1 Shut down loads 2 Perform shutdown operations on each UPS in the parallel system All inverters shut down at the same time and the parallel system transfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 3 Open the AC input circuit breaker on each UPS the gen...

Page 15: ...1 VOT Output voltage level 02 FRE Output frequency system 03 BVU Maximum bypass voltage 04 BVL Minimum bypass voltage 05 NO Number of batteries 06 CAP Total battery capacity 07 CL Charge current limit 08 EOD EOD mode 09 DT Discharge time protection setting 10 ECO ECO mode enabling 11 VU Maximum ECO voltage 12 VL Minimum ECO voltage 13 FR ECO frequency range 14 S P Single UPS or parallel system ava...

Page 16: ...ranges and no fault or alarm information is displayed If an alarm is present rectify the fault by checking the device status and parameters Abnormal noise No abnormal noise is generated Check where the abnormal noise comes from especially fans input and output transformer if configured If the problem is not resolved contact Huawei technical support Cleanliness Wipe the cabinet surface using a whit...

Page 17: ...and current of the battery string as well as the voltage of each battery 3 Check the battery surface temperature 4 Keep deformed and bulged faulty batteries still for 30 minutes and then check and record open circuit voltage of the faulty battery 5 If the fault persists contact Huawei technical support Battery management parameters Parameters settings of battery number battery capacity battery cha...

Page 18: ...ads and restart the UPS The Mains indicator is off The mains voltage or frequency exceeds the UPS input range Use a multimeter to check that the input voltage and frequency meet specifications The battery discharge time is much less than the standard time Batteries are not fully charged The battery performance deteriorates Charge batteries for more than 8 hours when the mains is normal Test the di...

Page 19: ...ecome normal and manually clear the alarm Abnorma l BPS volt 0A 1 Possible cause The bypass input voltage is abnormal Measure Check whether the bypass input voltage is out of the specified range If the voltage is out of the specified range change the range setting or wait for the bypass input to recover 2 Possible cause The bypass frequency is out of the 45 55 Hz mapping to 50 Hz or 55 65 Hz mappi...

Page 20: ...leared Possible cause The number of batteries configured is less than the actual number of batteries Measure Check whether the number of batteries is correctly set Battery overvoltage protection 20 1 Possible cause The number of batteries configured is less than the actual number of batteries Measure Check that the configured number of batteries is consistent with the actual number Possible cause ...

Page 21: ...nected are loose Measure Check that parallel cables are securely connected Possible cause Parallel cables are damaged Measure Replace the parallel cables 2 4 5 Parallel cable alarm 54 2 Possible cause The parallel cables connected are loose Measure Check that parallel cables are securely connected Possible cause The parallel cables are damaged Measure Replace the parallel cables 3 EPO 55 1 Possibl...

Reviews: