Ala
rm
ID
Alarm
Name
Alarm
Severit
y
Possible Cause
Suggestion
305
Abnorma
l Grid
Frequenc
y
Major
Cause ID = 2
The actual grid frequency
is higher than the standard
requirement for the local
power grid.
Cause ID = 4
The actual grid frequency
is lower than the standard
requirement for the local
power grid.
Cause ID = 5
The actual change rate of
the grid frequency does not
meet the standard
requirement for the local
power grid.
Cause ID = 2/4
1.
If the alarm occurs accidentally, the power
grid may be abnormal temporarily. The
SUN2000 automatically recovers after
detecting that the power grid becomes
normal.
2.
If the alarm occurs frequently, check
whether the grid frequency is within the
acceptable range. If no, contact the local
power operator. If yes, log in to the
SUN2000 app, SmartLogger, or NMS to
modify the grid overfrequency and
underfrequency protection thresholds with
the consent of the local power operator.
Cause ID = 5
1.
If the alarm occurs accidentally, the power
grid may be abnormal temporarily. The
SUN2000 automatically recovers after
detecting that the power grid becomes
normal.
2.
If the alarm occurs frequently, check
whether the grid frequency is within the
acceptable range. If no, contact the local
power operator.
313
Low
Insulatio
n
Resistanc
e
Major
Cause ID = 1
A short circuit occurs
between the PV string and
the PGND cable.
The PV string is installed
in a moist environment for
a long time.
1.
Check the impedance between the PV
string and the PGND cable. If a short
circuit occurs, rectify the fault.
2.
If you are sure that the impedance is less
than the default value in a cloudy or rainy
environment, log in to the SUN2000 app,
SmartLogger, or NMS and set
Insulation
resistance protection
.
318
Abnorma
l
Residual
Current
Major
Cause ID = 1
The insulation resistance
against the PGND cable at the
input side decreases when the
SUN2000 is running, which
causes an excessively high
residual current.
1.
If the alarm occurs accidentally, the
external circuit may be abnormal
temporarily. The SUN2000 automatically
recovers after fault is rectified.
2.
If the alarm occurs repeatedly or persists,
check whether the impedance between the
PV string and the ground is excessively
low.