6 System Commissioning
Issue 07 (2018-05-06)
Copyright © Huawei Technologies Co., Ltd.
72
Figure 6-8
Quick Settings screen (logging in as an advanced user)
Set the power grid code that applies to the country or region where the power station is located and
the inverter model.
Set user parameters based on the current date and time.
Set
Baud rate
,
RS485 protocol
, and
Address
based on site requirements.
Baud rate
can be set to
4800
,
9600
, or
19200
.
RS485 protocol
can be set to
MODBUS RTU
, and
Address
can be set to any
value in the range of 1 to 247.
When multiple inverters communicate with the SmartLogger over RS485, the addresses for all the
inverters on each RS485 route must be within the address range set on the SmartLogger and cannot
be duplicate. Otherwise, the communication will fail. In addition, the baud rates of all the inverters
on each RS485 route must be consistent with the SmartLogger baud rate.