SUN2000-43KTL-IN-C1
User Manual
4 System Installation
Issue 07 (2018-05-06)
Copyright © Huawei Technologies Co., Ltd.
33
Installation Angle Requirements
Install the SUN2000 vertically or at a maximum back tilt of 15 degrees to facilitate heat
dissipation.
Figure 4-21
Correct installation angles
Do not install the SUN2000 at a front tilt, excessive back tilt, side tilt, horizontally, or
upside down.
Figure 4-22
Incorrect installation angles
Installation Space Requirements
The SUN2000 dimensions (W x H x D, including the mounting bracket) are 930 mm x 550
mm x 283 mm. Reserve enough clearance around the SUN2000 to ensure sufficient space for
installation and heat dissipation, as shown in