SMU01C
User Manual
A LCD menu
Issue 03 (2015-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
42
A
LCD menu
Table A-1
LCD menu
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default Value Range
Alarm & Status
Active Alarm
Major Alarm
-
-
-
Minor Alarm
-
-
-
History Alarm
-
-
-
-
Rect Info
-
-
-
-
Version Info
-
-
-
-
SN Info
-
-
-
-
Settings
Batt Settings
Batt String
-
1
0–1
Capacity
-
40AH
5 AH–1000 AH
Charge Coef
-
0.15C10
0.05
C10–0.25C10
Com Settings
Address
-
0
0-30
COM Port
Baud
9600
9600, 19200
RS485/RS232
Port
Baud
9600
9600, 19200
Mode Select
Slave
Slave, Master
DC Settings
FC Volt
-
53.5V
47.0 V–56.5 V
(≤ BC Volt)
BC Volt
-
56.5V
53.5 V–57.0 V
(FC Volt ≤ BC
Volt ≤ DC Over
Volt – 1 V)
Over Volt
-
58.0V
58.0 V–60.0 V
Under Volt
-
45.0V
43.1 V–51.5 V
(LLVD Volt ≤