Alarm Management
9.1 Alarm Setting
Table 9-1 lists alarms for the SMU01C. You can set the alarm dry contact input port, alarm
severity, alarm dry contact output port.
Table 9-1
Alarm list
Alarm
Default Alarm Severity
Related Dry Contact
Mains Fault
Major
None
AC Over Volt
Minor
None
AC Under Volt
Minor
None
DC Under Volt
Major
None
DC Over Volt
Major
None
Batt Over Temp
Minor
None
Batt Under Temp
Minor
None
Amb.Over Temp 1
Minor
None
Amb.Under Temp 1
Minor
None
Amb.Over Temp 2
None
None
Amb.Under Temp 2
None
None
Amb.Over Humi
Minor
None
Amb.Under Humi
Minor
None
Door Alarm
Cleared
None
Water Inrush
Major
None
Smoke Alarm
Major
None
Batt Discharge
Minor
None
Batt Over Curr
Minor
None