SMU01C
User Manual
9 Alarm Management
Issue 03 (2015-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
38
Measures
1.
Adjust the ambient temperature alarm threshold to a proper range.
2.
Replace the faulty temperature sensor.
9.5.10 Batt Operation
Possible Causes
An AC outage occurs.
A rectifier is faulty.
Measures
Check whether an alarm is generated for an AC outage or a faulty rectifier. Rectifier the fault
by referring to related troubleshooting measures.
9.5.11 Batt Over Curr
Possible Causes
The rectifier fails to communicate with the monitoring unit.
Storage batteries are faulty.
Measures
1.
If a rectifier is not connected properly, reset and secure it.
2.
Check the storage batteries, and replace faulty ones.
9.5.12 Load Fuse Trip
Possible Causes
The load circuit breaker is OFF.
The circuit breaker detection wire is loose.
Measures
1.
Check the load circuit breaker. If the load circuit breaker is off but not because of short
circuit, switch on the load circuit breaker.
2.
If the circuit breaker detection wire is loose, secure it.
3.
Check whether the voltage at both ends of the circuit breaker is near 0 V using a
multimeter. If yes, the circuit breaker is functional. If no, replace the circuit breaker
because it is faulty.
4.
If the alarm persists after the load circuit breaker is replaced, replace the monitoring unit
because the alarm loop is faulty.
9.5.13 Batt. loop Trip
Possible Causes
The battery circuit breaker is OFF
.