SMU01C
User Manual
9 Alarm Management
Issue 03 (2015-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
37
9.5.6 Batt Over Temp
Possible Causes
Temperature inside the battery compartment exceeds the alarm threshold.
The battery temperature or ambient temperature alarm threshold is not properly set on
the monitoring unit.
The temperature sensor is faulty.
Measures
1.
Lower the temperature inside the battery compartment. The alarm is automatically
cleared after the temperature lowers to a proper range.
2.
Adjust the battery temperature alarm threshold to a proper range.
3.
Replace the faulty temperature sensor.
9.5.7 Batt Under Temp
Possible Causes
The battery temperature alarm threshold is not properly set on the monitoring unit.
The heater is faulty.
The temperature sensor is faulty.
Measures
1.
Adjust the battery temperature alarm threshold to a proper range.
2.
Replace the heater if an alarm is generated for a faulty heater.
3.
Replace the faulty temperature sensor.
9.5.8 Amb.Over Temp
Possible Causes
The ambient temperature exceeds the upper threshold.
The ambient temperature alarm threshold is not properly set on the monitoring unit.
The temperature sensor is faulty.
Measures
1.
Adjust the ambient temperature alarm threshold to a proper range.
2.
Replace the faulty temperature sensor.
9.5.9 Amb.Under Temp
Possible Causes
Ambient temperature alarm threshold is not properly set on the monitoring unit.
The temperature sensor is faulty.