5 Electrical Connections
Issue 05 (2019-01-20)
Copyright © Huawei Technologies Co., Ltd.
57
5.4 Connecting the Cabinet PE Cable
Procedure
Step 1
Crimp an OT terminal.
Step 2
Secure the PE cable.
Connect the PE cable to the nearest ground point or the ground bar in the box-type transformer.
Figure 5-6
Connecting a PGND cable
----End
Follow-up Procedure
To enhance the corrosion resistance of a ground terminal, you are advised to apply silica gel
or paint on it after connecting the ground cable.