Unit: mm
Installation Holes for U32 and Multi-Purpose Fiber Management
Cabinet on the ESD Floor
75 mm
75 mm
Multi-purpose fiber
management cabinet
U32 Enhanced support
Multi-purpose fiber
management cabinet
U32 Enhanced
Front
Back
33
ESD Floor : Installing Multi-Purpose Fiber Management Cabinets
Supports
Install multi-purpose fiber management cabinets supports.
Adjust the height of the multi-purpose fiber management cabinets supports to ensure that they are in the same
height as the U32 support. Partially tighten the height locking bolts.
If a support is not level, place spacers under the support. Tighten the expansion bolts using a torque socket.
Check that all supports are level using a level.