32
11 Routing Cables
•
You must use corrugated tube to protect core wires of optical cables in the cabinet, and use the binding strap
to bind optical fibers; do not drag or bind the optical fiber too tightly.
•
The bending radius of the optical cable core or optical fiber must be 20 times larger than the diameter of the
optical cable core or optical fiber. Generally, the bending radius is larger than or equal to 40 mm.
•
Only the qualified personnel are allowed to splice the optical fiber. Ensure that the optical fiber is spliced
according to the on-site requirements and local practice.
11.7 Routing the Optical Cable or Optical Fiber (Upstream)
Do not look into the optical port without eye protection.
Cable hole for optical cable
Cable hole for optical cable
Front door side of the cabinet
Install the adapters attached to
the cabinet on the installation
rack of
the adapter.
Steel wire must be connected to the grounding point.
Grounding point
(for the optical
cable)
Steel wire
Optical cable
To the ODF outside the cabinet
Battery compartment bottom (top view)
Cabinet bottom (top view)
Front door side of the cabinet
Optical cable