An all-polarity disconnection device is installed on the power supply side of the site. Shut off the AC input, and
attach labels on the switches that will be set during the cabling work.
•
Insulate the AC terminals and all unnecessary bare parts.
•
The cross-sectional area of AC power cable is not less than 10 mm2.
• The L and N wires of the power cable cannot be reversely connected.
25
11 Routing Cables
11.2 Routing the AC Power Cable
Battery compartment bottom (top view)
Cable hole of AC power cable
External AC power cable with 2 core wires (L
wire, N wire)
External AC power cable with 3 core wires
(PE wire, L wire, N wire)
AC power cable
To AC mains
AC power cable
PE wire
To AC mains
Cabinet bottom (top view)
Front door side of the cabinet
Front door side of the cabinet
Cable hole of AC power cable