Cable Type
Maximum
Current (A)
Minimum Cross-
Sectional Area
(mm
2
)
Maximum Cross-
Sectional Area
(mm
2
)
40
6
16
50
10
16
63
10
16
80
10
35
100
16
35
Battery cable
100
16
35
NOTE
● The data in the table is applicable when the ambient temperature is 30°C (in air) and cables are in a single
loop.
● When the ambient temperature is not 30°C or cables in multiple loops are routed together, use cables with
larger cross-sectional areas if the cabling distance is long.
● Battery cables should be able to withstand a temperature of at least 90°C.
4.1.2 Tools
NO TICE
Use tools with insulated handles. The following table is for reference only.
Table 4-2 Installation tools and instruments
ETP4860-B1A2 Embedded Power
User Manual
4 Installation
Issue 04 (2021-01-05)
Copyright © Huawei Technologies Co., Ltd.
35