Exporting Fault Logs
You can export fault logs on the LIVE-C APP to quickly collect information and
locate system faults.
Path: OM Tool > Fault Information
Exporting E-label Information
You can view and export e-label information about the power subrack, monitoring
board, and rectifier on the LIVE-C APP.
Path: OM Tool > E-label
7.3 Routine Maintenance
Perform routine maintenance based on site requirements. The recommended
maintenance interval is six months.
Table 7-1 Routine maintenance checklist
Maintenance
Item
Maintenance
Task
Check Method
Scenario for
Repair
Measures
Electricity
The AC input
voltage is normal.
Clamp meter
The AC input
voltage is beyond
the normal range.
For details, see
.
The output
voltage is normal.
The battery branch
or load branch
voltage exceeds
the specified range
(-42 V DC to -58 V
DC).
Preventive
maintenance
inspection
The indicators are
normal.
Observe
indicators
Alarms are
generated.
Grounding
The ground point
properly connects
to the ground bar
in the cabinet.
Clamp meter
The resistance
between the
ground point and
the ground bar is
greater than 0.1
ohm.
Secure the
ground cable to
the ground
point again or
replace the
ground cable.
7.4 Identifying Component Faults
7.4.1 Identifying Rectifier Faults
The following lists the rectifier faults
ETP4860-B1A2 Embedded Power
User Manual
7 Maintenance
Issue 04 (2021-01-05)