7.2.21 Rect Comm Fault
Possible Causes
A rectifier has been removed.
Rectifier connections are loose.
A rectifier is faulty.
Measures
1.
Check whether a rectifier has been removed. If so, reinstall it.
2.
If the rectifier is in position, remove the rectifier and reinstall it.
3.
If the alarm persists, replace the rectifier.
7.3 Identifying Faults
7.3.1 Identifying Rectifier Faults
Table 7-2
Identifying rectifier faults
Symptom
Possible Cause
Corrective Measures
The Run indicator (green)
is off.
There is no AC input, or
the rectifier is faulty.
Check whether the AC input
is normal. If the AC input is
normal, replace the rectifier.
If the AC input is normal and
the green indicators on all
rectifiers are off, replace the
AC/DC power distribution
subrack.
The Run indicator (green)
is blinking (0.5 Hz).
The rectifier is being
queried manually.
Exit the query status. The Run
indicator becomes steady on
again.
The Run indicator (green)
is blinking (4 Hz).
Software is being loaded.
After software finishes
loading, the indicator will
stop blinking, without any
user action required.
The Alarm indicator
(yellow) is steady on.
The rectifier is
protecting itself against
overtemperature.
The rectifier is
protecting itself against
AC input overvoltage or
undervoltage.
The rectifier is faulty.
If the ambient temperature
is higher than the upper
threshold, lower the
ambient temperature.
If the air intake or exhaust
vent is blocked, remove
the blockage.
If the AC input is
abnormal, ask
maintenance personnel for
the mains supply to rectify