ETP4830-A1 Embedded Power
User Manual
6 Commissioning
Issue 10 (2017-08-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
33
6.4 Setting System Type
If the SMU01A is configured, set the system type based on the actual situation, as described
in
Table 6-3
. If the SMU01B or SMU01C is configured, you do not need to reset the system
type.
Table 6-3
Setting system type
Main Menu
Second-Level
Menu
Third-level
Menu
Default Value Setting Value
Settings
Site Summary
System Type
Standard
ETP4830
6.5 Setting Battery Parameters
If battery parameters are incorrectly set, batteries will wear out earlier than necessary. Set the
parameters strictly according to requirements.
6.5.1 SMU01A
Set
Qty of Battery
to
1
, set
Rated Capacity
to the total capacity of battery strings, and set
Charge Coef
as required.
Table 6-4
Battery parameters for the SMU01A
Main Menu
Second-Level
Menu
Default Value
Settings
Quick Settings
Qty of Battery
1
1
Rated Capacity
65 Ah
Battery string
capacity
Charge Coef
0.15 C10
Range: 0.05
C10-0.25 C10
6.5.2 SMU01B and SMU01C
Set
Battery String
to
1
, set
Capacity
to the total capacity of battery strings, and set
Charge
Coef
as required.