6 Commissioning
Issue 10 (2017-08-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
36
6.8.2 SMU01B and SMU01C
Set the following alarm parameters as required if you need to enable the alarm function or
modify the alarm severity and relay association.
Table 6-10
Alarm parameters for the SMU01B and SMU01C
Main
Menu
Second-
Level
Menu
Third-
Level
Menu
Fourth-
Level
Menu
Default
Value
Setting
Settings
Alarm
Setting
Alarm
Severity
AC Volt
Low/High
NOTE
Take the
AC
Over Volt
alarm as an
example.
Major
Set the
parameter as
required.
Digital
Alarm
Digital No. 1
NOTE
Take
Digital No. 1
as an example.
Mode
High
Set the
parameter as
required.
Relay Relate
AC Volt Low/High (Alarm)
NOTE
Take the
AC Volt Low/High
alarm as an
example.
Relate Relay
None
Set the
parameter as
required.
Default type
NC
Set the
parameter as
required.
6.9 (Optional) Setting Communications Parameters
6.9.1 SMU01A
Setting Parameters Before Using WebUI
Before you use the WebUI to remotely manage the SMU01A, set the required IP parameters.
Procedure
Step 1
Apply to the site or equipment room network administrator for a fixed IP address.