ETP4830-A1 Embedded Power
User Manual
3 Components
Issue 10 (2017-08-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10
Figure 3-2
Rectifier
(1) Run indicator
(2) Alarm indicator
(3) Fault indicator
(4) Locking latch
(5) Handle
Table 3-1
Rectifier indicator description
Indicator
Color
Status
Description
Run indicator
Green
Steady on The rectifier has an AC power input.
Off
The rectifier has no AC power input.
The rectifier is faulty.
Blinking
at 0.5 Hz
The rectifier is being queried.
Blinking
at 4 Hz
The rectifier is loading an application
program.
Alarm indicator
Yellow
Off
No alarm has been generated.
Steady on
The rectifier has generated an alarm for
power limiting due to ambient
overtemperature.
The rectifier has generated an alarm for
shutdown due to ambient overtemperature
or undertemperature.
The rectifier is protecting itself against AC
input overvoltage or undervoltage.
The rectifier is hibernating.
Blinking
at 0.5 Hz
The communication between the rectifier and
the SMU has been interrupted.
Fault indicator
Red
Off
The rectifier is running properly.
Steady on The rectifier has been locked out due to