ETP4830-A1 Embedded Power
User Manual
6 Commissioning
Issue 10 (2017-08-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
38
Main Menu
Second-Level
Menu
Default Value
Settings
Gateway
192.168.0.1
Set this parameter
according to the
address assigned by
the network
administrator.
Step 3
Set the IP addresses and ports for the active and standby servers of the NetEco on the SMU's
LCD.
Table 6-13
NetEco parameters
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Default Value Settings
Settings
Comm Para
NetEco Main
IP
58.251.159.136
Set an IP address for the
active NetEco server.
NetEco Bak IP
58.251.159.136
Set an IP address for the
standby NetEco server.
NetEco Port
31220
Set a port for the NetEco.
----End
Setting Parameters Before SNMP Management
Before you use SNMP to perform remote management, set the required parameters.
Procedure
Step 1
Apply to the site or equipment room network administrator for a fixed IP address.
Step 2
Set the IP address, subnet mask, and gateway on the LCD, as described in
Table 6-14
.
Table 6-14
IP parameters
Main Menu
Second-Level
Menu
Default Value
Setting
Quick Settings
IP Address
192.168.0.10
Set this parameter
according to the
address assigned by
the network
administrator.
Subnet mask
255.255.255.0
Set this parameter
according to the
address assigned by