Figure 6-22
Components of an OT terminal and a power cable
A. Heat-shrinkable tubing
B. Bare crimping terminal
C. Insulation
D. Conductor
Procedure
Step 1
Based on the cross-sectional area of the cable conductor, strip a length of insulation coating C
to expose the conductor D of length L1, as shown in
. The recommended values
of L1 are listed in
.
Figure 6-23
Stripping a power cable (OT terminal)
l
When you strip a power cable, do not damage the conductor of the cable.
l
If the bare crimping terminal is not provided by Huawei, the value of L1 is 1 mm (0.04 in.)
to 2 mm (0.08 in.) greater than the value of L.
AP8082DN and AP8182DN
Hardware Installation and Maintenance Guide