67
LP- 293 REV. 9.2.14
ELITE FAN SPEEDS
MODEL
IGNITION
MIN
MAX
80
3000
1700
4600
110
3800
1700
4950
150
3800
1700
5200
220
3000
1450
4900
299/301
3000
1450
5000
399
3000
1600
6650
Table 26
PART 11 – TROUBLESHOOTING
A. BOILER ERROR CODE
If any of the sensors detect an abnormal condition, or an internal component fails during the operation of the boiler, the display may
show an error message and error code. This message and code may be the result of a temporary condition, in which case the display
will revert to its normal readout when the condition is corrected, or it may be a condition that the controller has evaluated as not safe to
restart the boiler. In this case, the boiler control will be locked out, the red FAULT light will be lit, and the mes
sage “LOCKOUT” will be
displayed on the readout on the lower line.
The Boiler will not start until a qualified technician has repaired the boiler and pressed the RESET button for more than 1 second. If
there is an error message displayed on the readout, and the mes
sage “LOCKOUT” is not displayed and the FAULT light is not lit, then
the message is the result of a temporary condition and will disappear when the problem corrects itself.
IMPORTANT NOTE: If you see error messages on your display readout, call a technician immediately, since the message may indicate
a more serious problem will occur soon.
B. BOILER ERROR
When an error condition occurs, the controller will display a description and code on the display readout. These error messages and
their recommended corrective actions are described in Section D.
C. BOILER FAULT
1. When a fault condition oc
curs, the controller will illuminate the red “FAULT” indication light and display a fault message in the screen.
The alarm output will also activate. Most fault conditions cause the CH pump to run in an attempt to cool the boiler.
2. Note the fault message displayed and refer to Section D in this part for an explanation of the message along with several
suggestions for corrective actions.
3. Press the reset key to clear the fault and resume operation. Be sure to observe the operation of the unit for a period of time to assure
correct operation and no reoccurrence of fault message.
When servicing or replacing any components of this boiler, be certain that:
The gas is off.
All electrical power is disconnected.
When servicing or replacing components that are in direct contact with boiler water, be certain that:
There is no pressure in the boiler. (Pull the release on the relief valve. Do not depend on the pressure gauge reading.
The boiler water is not hot.
The electrical power is disconnected.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN SUBMERGED IN WATER.
Immediately call a qualified service technician.
The appliance MUST BE replaced if it has been submerged. Attempting to operate an appliance that has been submerged could create
numerous harmful conditions, such as a potential gas leakage causing a fire and/or explosion, or the release of mold, bacteria, or other
harmful particulates into the air. Operating a previously submerged appliance could result in property damage, severe personal injury,
or death.
NOTE:
Appliance damage due to flood or submersion is considered an Act of God, and IS NOT covered under product warranty.
Summary of Contents for EL-110
Page 13: ...13 LP 293 REV 9 2 14 Figure 3 LP 285 B ...
Page 51: ...51 LP 293 REV 9 2 14 Figure 29 Cascade Master and Follower ...
Page 52: ...52 LP 293 REV 9 2 14 Figure 30 ...
Page 53: ...53 LP 293 REV 9 2 14 Figure 31 ...
Page 54: ...54 LP 293 REV 9 2 14 Figure 32 ...
Page 77: ...77 LP 293 REV 9 2 14 Figure 36 ...
Page 78: ...78 LP 293 REV 9 2 14 Figure 37 ...
Page 79: ...79 LP 293 REV 9 2 14 Figure 38 LP 293 A ...
Page 82: ...82 LP 293 REV 9 2 14 ...
Page 83: ...83 LP 293 REV 9 2 14 ...