The latest version of the National Electrical Code, NFPA No. 70.
NOTE:
The gas manifold and controls met safe lighting and other performance criteria when the boiler underwent tests specified in
ANSI Z21.13
– latest edition.
The hydronic supply and return connections of these products are for installation in closed loop systems ONLY!
Use of this
product in any manner other than described in this manual may result in premature product failure, substantial property damage, severe
personal injury, or death. Damage or failure of this product (or the system in which it is installed) due to unauthorized use
IS NOT
COVERED BY WARRANTY
.
NOTICE
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, HTP, Inc. has provided this boiler with
multiple features designed to save energy by reducing the boiler water temperature as heating load decreases.
These features include:
A modulating combustion system that adjusts firing rate based on heat demand.
Adjustment of boiler set point based on inferred heat load as determined by an outdoor sensor. The outdoor sensor
is supplied by HTP, Inc. with this boiler.
This boiler does not include a standing pilot.
This boiler is designed and shipped to assure the highest efficiency operation possible. Such high efficiency is
achieved by limiting heating circuit water temperature to 140°F when there is no anticipated heat load, based upon
the outdoor sensor and the Outdoor Reset Curve (sensor response curve) in the boiler software.
This feature may be over-ridden as described below in specific installations:
The boiler control is equipped with an outdoor sensor override for use with building management systems or in
cascaded systems (for systems with total input of 300,000 BTU/hr or greater).
See statement below for an important notice on the use of the override.
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a feature that
saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an
override which is provided primarily to permit the use of an external energy management system that serves the same
function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is installed that reduces the boiler water temperature as the heating load
decreases.
This boiler is not used for space heating.
This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
This boiler is equipped with a tankless coil.
NOTICE
The CSD-1 ASME Code, Section CW-400 requires that hot water heating and supply boilers have a) a UL 353 temperature control
device, b) at least one (1) temperature-actuated control to shut off the fuel supply when system water reaches a preset operating
temperature, c) a high temperature limit control that prevents the water temperature from exceeding the maximum allowable
temperature by causing a safety shutdown and lockout, and d) its own sensing element and operating switch.
The temperature control system integrated into the 926 control provided with this heating appliance complies with the requirements of
CSD-1 Section CW-400 as a temperature operation control. The control monitors the temperature difference between the inlet and the
outlet sensor, which is affected by boiler water flow. If this temperature difference exceeds 55°F (typically because of low water flow or
very low heat load), the control will reduce the maximum fan speed. If the temperature difference exceeds 60°F, the control will
effectively sense there is little or no water flow or heat load and shut the boiler down. The controller will restart automatically once the
temperature difference has dropped below 55°F and the minimum off time (anti-cycle time) has expired. In addition, if the control
senses that the outlet water temperature has reached 210°F, the boiler is put into a hard lockout and requires manual reset to restart.
TABLE OF CONTENTS
PART 1
– GENERAL SAFETY INFORMATION .......................................................................................................................... 7
A. PRECAUTIONS .......................................................................................................................................................................... 7
B. IMPROPER COMBUSTION ....................................................................................................................................................... 8
Summary of Contents for EL-110
Page 13: ...13 LP 293 REV 9 2 14 Figure 3 LP 285 B ...
Page 51: ...51 LP 293 REV 9 2 14 Figure 29 Cascade Master and Follower ...
Page 52: ...52 LP 293 REV 9 2 14 Figure 30 ...
Page 53: ...53 LP 293 REV 9 2 14 Figure 31 ...
Page 54: ...54 LP 293 REV 9 2 14 Figure 32 ...
Page 77: ...77 LP 293 REV 9 2 14 Figure 36 ...
Page 78: ...78 LP 293 REV 9 2 14 Figure 37 ...
Page 79: ...79 LP 293 REV 9 2 14 Figure 38 LP 293 A ...
Page 82: ...82 LP 293 REV 9 2 14 ...
Page 83: ...83 LP 293 REV 9 2 14 ...