Ensure that the intake air will not contain any of the contaminants below. For example, do not pipe intake near a swimming pool. Avoid
areas subject to exhaust fumes from laundry facilities. These areas always contain contaminants. Contaminated air will damage the
boiler, resulting in possible substantial property damage, severe personal injury, or death.
PRODUCTS TO AVOID
AREAS LIKELY TO HAVE CONTAMINANTS
Spray cans containing fluorocarbons
Dry cleaning/laundry areas and establishments
Permanent wave solutions
Swimming pools
Chlorinated waxes/cleaners
Metal fabrication plants
Chlorine-based swimming pool chemicals
Beauty shops
Calcium chloride used for thawing
Refrigeration repair shops
Sodium chloride used for water softening
Photo processing plants
Refrigerant leaks
Auto body shops
Paint or varnish removers
Plastic manufacturing plants
Hydrochloric or Muriatic acid
Furniture refinishing areas and establishments
Cements and glues
New building construction
Antistatic fabric softeners used in clothes dryers
Remodeling areas
Chlorine-type bleaches, laundry detergents, and cleaning solvents
Garages and workshops
Adhesives used to fasten building products
Table 1
NOTE: DAMAGE TO THE BOILER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY WARRANTY.
(Refer to the limited warranty for complete terms and conditions).
G. REMOVING A BOILER FROM A COMMON VENT SYSTEM
Do not install the boiler into a common vent with any other appliance. This
will cause flue gas spillage or appliance malfunction, resulting in possible
substantial property damage, severe personal injury, or death.
Failure to follow all instructions can result in flue gas spillage and carbon
monoxide emissions, causing severe personal injury or death.
When removing an existing boiler, the following steps must be followed.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch to
determine if there is blockage, leakage, corrosion or other deficiencies that could
cause an unsafe condition.
3. If practical, close all building doors, windows and all doors between the common
venting system and other spaces in the building. Turn on clothes dryers and any appliances not connected to the common venting
system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, at maximum speed. Do not operate a summer
exhaust fan. Close all fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust the thermostat so the appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or
smoke from a cigarette.
6. After it has been determined that each appliance remaining connected to common venting system properly vents when tested as
outlined, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms to the National Fuel Gas
Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to
approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z 223.1.
Figure 5 - CO Warning Label
Summary of Contents for EL-110
Page 13: ...13 LP 293 REV 9 2 14 Figure 3 LP 285 B ...
Page 51: ...51 LP 293 REV 9 2 14 Figure 29 Cascade Master and Follower ...
Page 52: ...52 LP 293 REV 9 2 14 Figure 30 ...
Page 53: ...53 LP 293 REV 9 2 14 Figure 31 ...
Page 54: ...54 LP 293 REV 9 2 14 Figure 32 ...
Page 77: ...77 LP 293 REV 9 2 14 Figure 36 ...
Page 78: ...78 LP 293 REV 9 2 14 Figure 37 ...
Page 79: ...79 LP 293 REV 9 2 14 Figure 38 LP 293 A ...
Page 82: ...82 LP 293 REV 9 2 14 ...
Page 83: ...83 LP 293 REV 9 2 14 ...