The control can be set up to monitor outdoor temperature through an outdoor sensor to regulate boiler set point. The system can be
further enhanced by installing an indirect water heater to provide domestic hot water.
The control can regulate the output of multiple boilers through its cascade system function. The cascade system is capable of
connecting up to eight boilers together in such a way that they function as one boiler system. This allows for greater turn down ratios
and provides systematic control of the multiple boilers in an installation to minimize downtime and maximize efficiency.
The cascade system works by establishing one boiler as the master and the other connected boilers as followers. The master boiler
requires a sensor to provide feedback on set point temperature in order to adjust heating input from the connected boilers. Each
cascaded boiler will have its own pump to provide maximum flow and control heat exchanger flow rate.
Text Display and Operational LED Light Indicators
– The display allows the user to change system parameters and monitor system
outputs.
Gas Valve
– Senses suction from the blower, allowing gas to flow only if powered and combustion air is flowing.
All Metal Integrated Venturi
– Controls air and gas flow into the burner.
Burner
– Constructed of high grade stainless steel, the burner uses premixed air and gas fuel and provides a wide range of firing rates.
Spark Ignition
– The burner is ignited by applying high voltage through the system spark electrode. This causes the spark from the
electrode to ignite mixed gas off of the burner.
Supply Water Temperature Sensor
– This sensor monitors the boiler outlet water temperature (System Supply). The control adjusts
the boiler firing rate so the supply temperature will match the boiler set point.
Return Water Temperature Sensor
– This sensor monitors the boiler return water temperature (System Return).
Flue Sensor
– Monitors flue temperature and adjusts firing rate.
Temperature and Pressure Gauge
– Allows the user to monitor system temperature and pressure.
Electrical field connections with terminal strips
– The electrical cover allows easy access to the line voltage and low voltage
terminals strips which are clearly marked to facilitate wiring of the boiler.
Condensation Collection System
– This boiler is a high efficiency appliance, therefore the boiler will produce condensate. The
collection system has a float switch which monitors the condensation level and prevents condensation from backing up into the
combustion system. Inside the collection system there is a built in trap which seals the combustion system from the connected drain.
This condensate should be neutralized to avoid damage to the drainage system or piping.
Outdoor Sensor
– Monitors outdoor temperature and adjusts unit set point to provide greater efficiency.
0-10 Volt Input
– Allows Installer to connect a BMS (Building Management System) to control the boiler.
Condensate Flue Check System
– The check system prevents exhaust from the heat exchanger from backing up into cabinet.
Pump Service Mode
– Allows manual operation of pumps to commission system and check pump operation.
The Vision II System
(Optional)
– Allows the user to supply mixed temperatures in up to eight zones. The Vision II system controls the
temperature to each zone by employing three way mixing valves. The Vision II also controls the output temperature of the boiler to
assure accurate temperature delivery to all connected zones.
C. OPTIONAL EQUIPMENT
Below is a list of optional equipment available from HTP. These additional options may be purchased through your HTP distributor:
Wall Mount Bracket (Part # 7450P-211)
System Sensor (Part # 7250P-324)
Indirect Tank Sensor (Part # 7250P-325)
3" PVC Concentric Vent Kit (Part # KGAVT0601CVT)
3” Stainless Steel Outside Termination Vent Kit (Part # V1000)
4” Stainless Steel Outside Termination Vent Kit (Part # V2000)
6” Stainless Steel Outside Termination Vent Kit (Part # V3000)
3” Polypro Vent Kit (Part # 8400P-001)
3” Polypro Pipe (33’ length Part # 8400P-002, 49.5’ length Part # 8400P-003)
U.L. 353 Compliant Low Water Cut-Off Interface Kit with Manual Reset (Part # 7450P-225)
Manual Reset High Limit (Part # 7450P-217)
Summary of Contents for EL-110
Page 13: ...13 LP 293 REV 9 2 14 Figure 3 LP 285 B ...
Page 51: ...51 LP 293 REV 9 2 14 Figure 29 Cascade Master and Follower ...
Page 52: ...52 LP 293 REV 9 2 14 Figure 30 ...
Page 53: ...53 LP 293 REV 9 2 14 Figure 31 ...
Page 54: ...54 LP 293 REV 9 2 14 Figure 32 ...
Page 77: ...77 LP 293 REV 9 2 14 Figure 36 ...
Page 78: ...78 LP 293 REV 9 2 14 Figure 37 ...
Page 79: ...79 LP 293 REV 9 2 14 Figure 38 LP 293 A ...
Page 82: ...82 LP 293 REV 9 2 14 ...
Page 83: ...83 LP 293 REV 9 2 14 ...