I-V400w - I-V500w - SOLAR I-Vw - SOLAR I-Ve
EN - 40
22. The instrument displays:
Vdc = DC output voltage from module/string.
Irr = irradiance measured by supplied reference cell
Tc = temperature of module. The herewith options are
available for this field:
AUTO
automatic mode of temperature measurement
Number
MAN or AUX mode of temp. measurement
“ - - - “
AUX mode with no connected probe
Module = type of selected module
Temp = measurement mode of module temperature
Start = measurement activation mode
The symbol “
”
fixed
at display means that a stable
RF connection is established with the SOLAR-02
15/05/10 15:34:26
V d c
=
3 6 7
V
I r r
=
1 0 4 5
W / m 2
T c
=
4 5
° C
Module: SUNPOWER 210
Temp: Auto
Start: Manual
Select
I – V
CAUTION
At the press of
GO/STOP
key some different error messages can be
displayed by the meter (see § 6.3) and, due of this, the test cannot start.
Check and remove, if possible, this error message before start the test
23. Press
GO/STOP
key (in Manual activation mode) to start
the test. If none of the previous error messages are
detected, the message “
Measuring…
” is shown on the
display for some seconds, depending on the level of
power during test.
15/05/10 15:34:26
V d c
=
3 6 7
V
I r r
=
1 0 4 5
W / m 2
Tc
=
45
°C
Module: SUNPOWER 210
Measuring…
Select
I - V
24. At the end of test, the values of typical parameters (all
referred to a single module in standard conditions STC)
are shown by the meter together with the final response (§
6.2.3) based on the automatic calculation performed and
relevant to:
Translation of I-V curve to STC condition
Verification of tolerance % of the maximum power
declared by the manufacturer.
15/05/10 15:34:26
V o c =
1 5 . 2
V
V m p p = 1 4 . 7
V
I m p p = 4 . 7
A
I s c =
5 . 2
A
P m a x = 2 0 0
W
F F =
7 7 . 1
%
D P m a x =
2 . 1
%
Results @ STC – Response: OK
Select
I - V
25. Press
ENTER
for the visualization of measurement results
referred at STC or OPC conditions both in numeric and
graphical mode (§ 6.2.3)
26. Use the arrow key
for the selection of table or graph
visualization
27. Press
SAVE
key to store the result of test (see § 7.2) or
ESC/MENU
key to exit without saving and to go back to
the main menu
28. The “
Auto
” activation mode require to disconnect and
reconnect the test leads in order to start automatically a
new measurement
15/05/10 15:34:26
V o c =
1 5 . 2
V
V m p p = 1 4 . 7
V
I m p p = 4 . 7
A
I s c =
5 . 2
A
P m a x = 2 0 0
W
F F =
7 7 . 1
%
D P m a x =
2 . 1
%
T a b l e
G r a p h
– Response: OK
Select
I - V