HRS Hevac Ltd AquaSave A6 Range
Installation, Operating & Instruction Manual
Installation
3
3.1
Siting
The AquaSave hot water heater shall be installed in a dry place where room temperature is below 40°C,
and ideally in ventilated premises.
AquaSave is placed preferably on a sub-base footing.
3.2
Hydraulic connections
Connect the charging kit (exc control valve + charging pump) to the storage tank using the interlink kit.
Make arrangements for fitting the insulation onto the tank before connecting up the piping.
The indirect AquaSave module can run without a recirculation system fitted.
To avoid creating a galvanic coupling, check that the materials used in the installation have similar corrosion
potentials.
3.3
Basic assembly instrustions
Assembly: refer to the full instructions given in
17 Assembly of the charging kit to the AquaSTOR.
Connect the primary supply and return connections.
Connect the cold water supply, hot water outlet and the recirculation system to the tank.
Fit the tank with a safety valve, a drain valve in the top section and a draw-off in the bottom section.
NOTE:
The valve is a compulsory fixture that has to be pre-loaded at the storage tank operating pressure.
NOTE:
The safety valve on the charging kit only protects the secondary system – it will neither protect nor
surge-feed the installation and the volume stored, in correspondence with local rules.
The safety valve shall have the same diameter as the cold water inlet fixture
Top section connection
Exchanger s accessories