HRS Hevac Ltd AquaSave A6 Range
Installation, Operating & Instruction Manual
16.5 Set the number of pumps
The pumps’ configuration and connections is factory made.
In a servicing situation the correct pump must be identified.
Codification
Meaning
Connected pump(s)
A62B
1 charging pump
P3
A63B
1 primary pump + 1 charging pump
P1+P3
16.6 Add an extra sensor
Please see
6.2 Electrical wiring diagram, option A62B
and
6.3 Electrical wiring diagram, option A63B
S1-S3 are temperature sensors, NTC20k.
16.7 Connect to 230V Triac output
The 230V electrical output can be configured as a pulse
function. For example it can be used to shortly activate an
electrical drain valve.
In this configuration, the pulse duration can be programmed to
be active a day, week or special day.
For example each Sunday at 10h00 for 5 seconds.
See
9.9 230V Triac menu
.
Connected device must not exceed 230VAC 1A.
16.8 Add relay 1 and relay 2
Relay 1 can be NO (normally open) or NC (normally closed). Relay 2 is always NO (normally open).
Connect the relay 1:
Operating
mode
Connections on PCB bottom
terminal
NO
C-NO (25-24)
NC
C-NF (25-26)
Connect relay 2 to the controller terminal 13(IN6) and 14 (OUT6).
See
6.2 Electrical wiring diagram, option A62B
and
6.3 Electrical wiring diagram, option A63B
If using 230V phase through this contact, do not exceed 2A load.
16.9 Add a remote control contact
The AquaSave can be operated by a remote controller. To enable that connect a volt free contact between
BI1 and GND.
Wire terminal name
Wire terminal number
BI1
33
GND
31 or 37
NOTE
: When the contact is open, the unit operates normally. If it is closed the unit is in standby
(mode) but the controller display remains activated.
DO NOT power supply this contact! It is a volt free contact.
See
6.2 Electrical wiring diagram, option A62B
and
6.3 Electrical wiring diagram, option A63B