HRS Hevac Ltd AquaSave A6 Range
Installation, Operating & Instruction Manual
Electrical connections
5
All devices shall be connected up in compliance with the governing standards.
All work on control box and other electrical components must be done by qualified people.
The main electrical box should be equipped with short-circuits protection
5.1
A60B
The charging pump has to be powered constantly.
5.2
A62B & A63B
For more information about the Operator Control box, see chapter
6 Electrical installation of control box, option
,
and forward.
Power the control box via a single-phase 230 V + ground.
Electrical system components pre-cabled according to the hardware ordered.
5.3
Electrical power ratings table
Unit Type
Primary pump
type
Primary pump
consumption.
W, A
Secondary
pump type
Secondary
pump
consumption,
W
TOTAL +
Control box
1)
-
-
UP20-45N
115W 0.5A
125W
0.6A
2)
-
-
UPS 32-80N
240W 1.05A
245W
1.15A
2)
-
-
UP20-45N
115W 0.5A
125W
0.8A
-
UPS 32-80N
240W
1.05A
250W
1.17A
Magna 1 32-80
151W
1.22A
UP20-45N
115W
0.5A
266W
2.02A
Magna 1 32-80
151W
1.22A
UPS 32-80N
240W
1.05A
391W
2.57A
SINGLE-PHASE 230 VOLTS + GROUND
1)
The electrical consumption of the control box and the actuator is 10W, 0.3A.
Figures are rounded up to the nearest value.
2)
Has no control box
5.4
Current limiting fuses
Power cards are equipped with fuses, labelled FU1 to FU5 on the printed circuit.
Fuse
FU1
FU2
FU3
FU4
FU5
Protection
PUMP 1
N/A
PUMP
N/A
PCB
Size (mm)
6.3x32
6.3x32
6.3x32
6.3x32
6.3x32
Calibre
2.5A
2.5A
250mA
Voltage
250V
250V
250V
250V
250V
Safety fuses are supplied inside the control box.
A60B
80 - 200 kW
A60B
>200 kW
A62B
80 - 200 kW
A62B
>200 kW
A63B
80 - 200 kW
A63B
>200 kW