Chapter 5 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
50
―
HD3N-TC Series Inverter User Manual V1.0
Ref. code
Name Description
Setting Range [Default]
F15.18 DO1
function
0 - 206 [0]
F15.19 DO2
function
0 - 206 [2]
F15.20
RLY1 relay function
0 - 206 [200]
0:
Unused.
1: Inverter is ready. Inverter completes power on and no fault occurs, then it can normally run.
2: Inverter running. Inverter is in run status.
3: Forward running. Inverter is forward running.
4: Reverse running. Inverter is reverse running.
9,10: Frequency level detection signal (FDT1,FDT2).
•
Refer to F15.31 - F15.35.
26: Motor 1/2 indicator. Signal is valid when inverter controls motor 1, invalid when control motor 2.
29: Stop in under-voltage condition. When DC busbar voltage is lower than under-voltage level, output
indicating signal.
•
“-Lu-” is displayed on LED keypad.
31: Inverter fault. Inverter has fault.
32: External fault. Inverter detects external devcice has fault via terminal.
33: Fault of inverter is reset automatically.
38: High speed pulse output (DO2 only).
•
Refer to F16.21.
200: Brake output. Inverter outputs this signal when brake condition is met.
202: UP complete limit. When inverter receives UP complete limit. It outputs this signal.
203: DN complete limit. When inverter receives DN complete limit, it outputs this signal.
204: UP complete final limit. When inverter receives UP complete final limit, it outputs this signal.
205: DN complete final limit. When inverter receives DN complete final limit, it outputs this signal.
206: Brake fault output. When inverter has brake fault (E0030), it outputs this signal.
F15.24
Terminal output logic setting
0 - 0x7 [00]
Defines that each bit (binary) represents different physical sources.
•
0: Positive logic. Connected to corresponding common port: this logic is enabled. Otherwise disabled.
•
1: Negative logic. Connected to corresponding common port: this logic is disabled. Otherwise enabled.
F15.24
Bit3
Bit2
Bit1
Bit0
Frame3 / 4
- RLY1
DO2
DO1
Frame1 / 2
- RLY1
DO -
123
F15.30
FDT1 detection mode
0,1 [0]
0: Detect according to setting frequency.
1: Detect according to output frequency.
F15.31 FDT1
level
0.00 - Upper limit frequency
[5.00Hz]