Chapter 5 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
28
―
HD3N-TC Series Inverter User Manual V1.0
5.1
Group d: Display Parameter
Group d is status display parameter.
5.1.1
d00: Status Display Parameter
Ref. code
Name Description
Setting Range [Default]
d00.00 Inverter
series
[Actual value]
d00.01
Software version of inverter
[Actual value]
d00.03
Non-standard software version of inverter
[Actual value]
d00.06
Customized serial number
[Actual value]
d00.07
Motor and control mode
[Actual value]
Displays present motor and control mode.
Units: Current driving motor
•
0: Motor 1.
•
1: Motor 2.
Tens: Control mode
•
0: V/f control without PG.
•
1: Vector control 1without PG.
•
2,6: Vector control 2/3without PG.
d00.08
Rated current of inverter (A)
[Actual value]
d00.10 Inverter
status
[Actual value]
Displays the inverter status, as following:
Thous
ands
Bit15: Unused
Bit14: Unused
Bit13: Software
current restriction
0: Do not restrict
1: Restrict
Bit12: Stall
overvoltage
0: Invalid
1: Valid
Hundr
eds
Bit11: Unused
Bit10: Speed
limitation
0: Below limitation
1: Above limitation
Bit9: Unused
Bit8: Auto-tuning
0: Not in auto-tuning
1: In auto-tuning
Tens
Bit7: Unused
Bit6: Unused
Bit5&Bit4: Acc/Dec/Constant
00: Constant
11: Constant
01: Acc
10: Dec
Units
Bit3: Zero speed
0: Invalid
1: Valid
Bit2: Forward/Reverse
0: Forward
1: Reverse
Bit1: Run/Stop
0: Stop
1: Run
Bit0: Inverter fault
0: Faulty
1: Normal
123
d00.11
Main setting frequency channel
[Actual value]
0:
Keypad.
1: Terminal.
2: Communication.
6 - 7: AI1 - AI2.
10: Potentionmeter on keypad.
12: Multi-speed.
d00.14
Setting frequency (Hz)
[Actual value]