Facility requirements
Table 5: Facility requirements
Dimension
Value
Electrical
• Adequate supply circuit, line fusing, and wire size, as specified by the
electrical rating on the switch nameplate
• Circuit protected by a circuit breaker and grounded in accordance
with local electrical codes
For complete power supply specifications, see HPE StoreFabric
SN3600B 32Gb FC Switch or HPE StoreFabric SN6600B 32Gb FC
Switch power supply specifications table.
Thermal
•
HPE StoreFabric SN3600B 32Gb FC Switch
Maximum airflow of 54.5 cubic m/hr (32.1 cubic ft/min) available in
the immediate vicinity of the switch. Nominal: 36.35 cmh (21.4 cfm)
HPE StoreFabric SN6600B 32Gb FC Switch
Maximum airflow of 71.36 cubic m/hr (42 cubic ft/min) available in the
immediate vicinity of the switch. Nominal: 59.47 cmh (35 cfm)
• Ambient air temperature not exceeding 40°C (104°F) while the
switch is operating
Rack (when rack-mounted)
• 1U in a 48.3 cm (19 in) cabinet
• All equipment in rack grounded through a reliable branch circuit
connection
• Additional weight of switch not to exceed the rack’s weight limits
• Rack secured to ensure stability in case of unexpected movement
Power supply specifications
The power supplies are universal and operate worldwide without voltage jumpers or switches. They meet
IEC 61000-4-5 surge voltage requirements and support autoranging to accommodate input voltages and
line frequencies. Each power supply has built-in fans for cooling.
Table 6: HPE StoreFabric SN3600B 32Gb FC Switch and HPE StoreFabric
SN6600B 32Gb FC Switch power supply specifications
Specification
Values
Input voltage
Range: 90–264 VAC, Nominal: 100–240 VAC
Input frequency
Range: 47–63 Hz; Nominal: 50–60 Hz
Inrush current
Maximum of 50 A peak at 240 VAC
Table Continued
Facility requirements
31