Description
Chassis
Fan configuration
Number of drives
supported by the
server
Maximum inlet
ambient temperature
Ethernet
adapters with
QSFP28
transceiver/
InfiniBand
adapters with
EDR speed
Apollo
DX2200
Gen10
Chassis
(12 LFF
backplane)
Redundant and
nonredundant
Optical cable: Not
supported
Copper cable: 25°C
(77°F)
Optical cable: Not
supported
Copper cable: 22°C
(71.6°F)
Optical cable: 22°C
(71.6°F)
Copper cable: 35°C
(95°F)
Apollo
DX2600
Gen10
Chassis
(24 SFF or 16
SFF + 8
NVMe
backplane)
Redundant and
nonredundant
0 to 6 drives
Optical cable: 22°C
(71.6°F)
Copper cable: 35°C
(95°F)
Apollo
DX2800
Gen10
Chassis
(24 SFF
backplane
with SAS
expander)
Redundant and
nonredundant
0 to 24 drives
Optical cable: 22°C
(71.6°F)
Copper cable: 35°C
(95°F)
Apollo
DX2800
Gen10
Chassis
(16 NVMe
backplane)
Redundant and
nonredundant
0 to 4 drives
Optical cable: 22°C
(71.6°F)
Copper cable: 35°C
(95°F)
The drive capacity must be less than 10 TB.
The drive capacity must be greater than or equal to 10 TB.
If the component is installed in server 1 or server 2, and the server is installed in the Apollo DX2200 Gen10 Chassis,
drive blanks must be installed in drive bays 1-2 and 2-2. Similarly, if the component is installed in server 3 or server 4,
and the server is installed in the Apollo DX2200 Gen10 Chassis, drive blanks must be installed in drive bays 3-2 and
4-2.
126
Specifications