HPE 800W Flex Slot -48VDC Hot-plug Low Halogen Power Supply
HPE 800W Flex Slot -48VDC Hot-plug Low Halogen Power Supply
Specification
Specification
Value
Value
Input requirements
Input requirements
—
Rated input voltage
-40 VDC to -72 VDC
-48 VDC nominal input
Rated input current
22.1 A at -40 VDC input
18.2 A at -48 VDC input, nominal input
12.0 A at -72 VDC input
Rated input power (W)
874 W at -40 VDC input
865 W at -48 VDC input, nominal input
854 W at -72 VDC input
Rated input power (BTUs per hour)
2983 at -40 VDC input
2951 at -48 VDC input, nominal input
2912 at -72 VDC input
Power supply output
Power supply output
—
Rated steady-state power (W)
800 W at -40 VDC to -72 VDC
Maximum peak power (W)
800 W at -40 VDC to -72 VDC
Maximum peak power
800 W at -40 VDC to -72 VDC input
WARNING:
WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit
has no direct connection to a primary circuit and derives its power from a transformer,
converter, or equivalent isolation device.
The branch circuit overcurrent protection must be rated 27 A.
CAUTION:
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the
earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is
connected.
This equipment must be located in the same immediate area (such as adjacent cabinets) as any other equipment that
has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and also
the point of earthing of the DC system. The DC system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the
point of connection of the earthing electrode conductor.
HPE 800W Flex Slot -48VDC Hot-plug Low Halogen Power Supply
273
Summary of Contents for ProLiant DL360
Page 8: ...10 6 Documentation feedback...
Page 9: ...Illustrated parts catalog Illustrated parts catalog 9...
Page 20: ...Processor spare parts Processor spare parts 20...
Page 40: ...Expansion board spare parts Expansion board spare parts 40...
Page 78: ...Customer self repair 78...
Page 79: ...Customer self repair 79...
Page 80: ...Customer self repair 80...
Page 81: ...Customer self repair 81...
Page 82: ...Removal and replacement procedures Removal and replacement procedures 82...
Page 96: ...Removing and replacing the bezel Removing and replacing the bezel 96...
Page 102: ...7 Secure the cables Removing and replacing the ball bearing rails 102...
Page 125: ...Removing the Pensando DSP DSC 25 2p SFP28 card with the iLO Sideband ALOM Module 125...
Page 159: ...guidelines Removing and replacing a persistent memory module 159...
Page 191: ...Troubleshooting Troubleshooting 191...
Page 193: ...Diagnostic tools Diagnostic tools 193...
Page 206: ...Component identification Component identification 206...
Page 236: ...Smart Carrier NVMe SCN drive LED definitions 236...
Page 238: ...HPE Basic Drive LED definitions 238...
Page 241: ...BIOS Platform Configuration RBSU Hot plug fans 241...
Page 248: ...Cabling Cabling 248...
Page 253: ...SFF backplane to P824i p controller 253...
Page 255: ...2 SFF backplane to P816i a controller 2 SFF backplane to P816i a controller 255...
Page 256: ...10 SFF NVMe backplane to NVMe riser 10 SFF NVMe backplane to NVMe riser 256...
Page 257: ...2 SFF NVMe backplane to primary riser 2 SFF NVMe backplane to primary riser 257...
Page 258: ...1 SFF rear backplane to system board SATA 1 SFF rear backplane to system board SATA 258...
Page 259: ...10 SFF backplane to P408i a controller 10 SFF backplane to P408i a controller 259...
Page 263: ...4 LFF backplane to P408i a controller 4 LFF backplane to P408i a controller 263...
Page 265: ...Specifications Specifications 265...
Page 277: ...Support and other resources Support and other resources 277...