Removing and replacing a fan
Removing and replacing a fan
CAUTION:
CAUTION: Do not operate the server for long periods with the access panel open or removed. Operating the server in
this manner results in improper airflow and improper cooling that can lead to thermal damage.
IMPORTANT:
IMPORTANT: For optimum cooling, install fans in all primary fan locations.
Procedure
Procedure
1. Extend the server from the rack .
3. Remove the fan.
IMPORTANT:
IMPORTANT: When a hot-plug fan is removed, the other fans in the server will increase speed to compensate.
CAUTION:
CAUTION: To avoid server shutdown, a fan must be replaced within 60 seconds of being removed.
To replace the component, reverse the removal procedure.
Removing and replacing a fan
112
Summary of Contents for ProLiant DL360
Page 8: ...10 6 Documentation feedback...
Page 9: ...Illustrated parts catalog Illustrated parts catalog 9...
Page 20: ...Processor spare parts Processor spare parts 20...
Page 40: ...Expansion board spare parts Expansion board spare parts 40...
Page 78: ...Customer self repair 78...
Page 79: ...Customer self repair 79...
Page 80: ...Customer self repair 80...
Page 81: ...Customer self repair 81...
Page 82: ...Removal and replacement procedures Removal and replacement procedures 82...
Page 96: ...Removing and replacing the bezel Removing and replacing the bezel 96...
Page 102: ...7 Secure the cables Removing and replacing the ball bearing rails 102...
Page 125: ...Removing the Pensando DSP DSC 25 2p SFP28 card with the iLO Sideband ALOM Module 125...
Page 159: ...guidelines Removing and replacing a persistent memory module 159...
Page 191: ...Troubleshooting Troubleshooting 191...
Page 193: ...Diagnostic tools Diagnostic tools 193...
Page 206: ...Component identification Component identification 206...
Page 236: ...Smart Carrier NVMe SCN drive LED definitions 236...
Page 238: ...HPE Basic Drive LED definitions 238...
Page 241: ...BIOS Platform Configuration RBSU Hot plug fans 241...
Page 248: ...Cabling Cabling 248...
Page 253: ...SFF backplane to P824i p controller 253...
Page 255: ...2 SFF backplane to P816i a controller 2 SFF backplane to P816i a controller 255...
Page 256: ...10 SFF NVMe backplane to NVMe riser 10 SFF NVMe backplane to NVMe riser 256...
Page 257: ...2 SFF NVMe backplane to primary riser 2 SFF NVMe backplane to primary riser 257...
Page 258: ...1 SFF rear backplane to system board SATA 1 SFF rear backplane to system board SATA 258...
Page 259: ...10 SFF backplane to P408i a controller 10 SFF backplane to P408i a controller 259...
Page 263: ...4 LFF backplane to P408i a controller 4 LFF backplane to P408i a controller 263...
Page 265: ...Specifications Specifications 265...
Page 277: ...Support and other resources Support and other resources 277...