Troubleshooting 96
Deep Sleep mode
setting
Charger Limit is set to
any setting except
NO CHARGE
Charger Limit is set to
NO CHARGE and a
battery module has low
voltage
Charger Limit is set to NO
CHARGE and no battery
modules have low voltage
The UPS sets "Enter Deep
Sleep Mode."
Keep at Deep Sleep
mode.
Keep at Deep Sleep
mode.
Keep at Deep Sleep mode.
The UPS clears "Enter
Deep Sleep Mode."
Wake up.
Keep at Deep Sleep mode
until the handle of the
battery module is pressed
and the low-voltage
battery module is
replaced.
Wake up.
Reset the power on the power module to avoid dropping loads during troubleshooting.
1.
Set the power module to Bypass mode.
2.
Disconnect the power module.
3.
Reconnect the power module.
4.
Set the power module to Normal mode.