System Specifications
Electrical Specifications
Chapter 1
7
Electrical Specifications
This section provides electrical specifications for the system.
Circuit Breaker
The Marked Electrical for the HP Server is 13 amps. The recommended circuit breaker size is 15 amps for
North America. For countries outside North America, consult the local electrical authority that has
jurisdiction for the recommended circuit breaker size.
The system contains three power receptacles located at the bottom rear bulkhead. A minimum of two power
supplies/cords must be used to maintain normal operation of the system. A third power supply/cord can be
added to improve system availability by protecting, for example, against power source failures or accidentally
tripped circuit breakers.
System Power Requirements
Table 1-4
Power Requirements
Requirements
Value
Comments
Nominal input voltage
100-240 VAC
Frequency range (minimum - maximum)
50 - 60 HZ
Number of phases
1
Theoretical maximum current
11.2A
Per line cord
Maximum inrush current
35A
Per line cord
Power factor
0.98
Typical
Ground leakage current (mA)
< 1.75 mA
Per line cord